Skip to navigation

Threat reportVulnerabilityTL-2026-3583

CVE-2026-20764: OS Command Injection in Copeland XWEB Pro (hostname configuration) enables authenticated RCE

highMONITORING

An OS command injection vulnerability (CWE-78) in Copeland XWEB Pro 1.12.1 and prior (XWEB 300D PRO, 500D PRO, 500B PRO) lets an authenticated attacker achieve remote code execution through malicious input in the device hostname configuration. CISA reports no known public exploitation; Copeland has released a fix. First disclosed .

Key facts

IdentifiersTL-2026-3583, CVE-2026-20764, CVE-2026-23702, CVE-2026-24695
Also known asICSA-26-057-10
SeverityHIGH
CVSS8 (CVSS:3.1/AV:N/AC:H/PR:H/UI:N/S:C/C:H/I:H/A:H)
First disclosed
EPSSCVE-2026-20764: 2.1% (82.0th percentile); CVE-2026-23702: 2.0% (81.6th percentile); CVE-2026-24695: 1.7% (77.5th percentile)
Affected productsCopeland XWEB 300D PRO; Copeland XWEB 500D PRO; Copeland XWEB 500B PRO
Weaknesses (CWE)CWE-78
MITRE ATT&CK techniquesT1059 Command and Scripting Interpreter, T1078 Valid Accounts, T1190 Exploit Public-Facing Application
MotivationUNKNOWN
Target sectorscommercial facilities, retail, food and beverage, cold chain
Target regionsWorldwide
Detection rules9 (1 shown free)
Sources9 cited sources

Detection coverage

As of 2026-10-15, Threadlinqs Intelligence publishes 9 detection rule(s) for TL-2026-3583 across Splunk SPL, Microsoft KQL and Sigma, covering 8 indicator(s) of compromise. The whole corpus is readable without an account. Every threat comes with one complete detection in Splunk SPL, Microsoft KQL and Sigma, free for everyone; a free account adds daily TL Creds to unlock the rest. Paid plans add a larger daily allowance, correlation and the MCP server. Threadlinqs MCP server · View plans.

Free detection: CVE-2026-20764 XWEB Pro Hostname Command Injection — Shell Metacharacters in Hostname Parameter

Detects HTTP POST/PUT requests whose hostname parameter contains shell metacharacters (; | backtick $ && newline). CVE-2026-20764 (CWE-78) in Copeland XWEB 300D/500D/500B PRO firmware <=1.12.1 passes the configured hostname to system setup, so an authenticated attacker can execute OS commands. A legitimate hostname never contains these characters, making this a behaviour-first, low-noise signature of the exploit trigger.

  • Languages: Splunk SPL, Microsoft KQL, Sigma
  • ATT&CK: T1190, T1059.004, T1078
  • Data sources: splunk_stream_http (index=network sourcetype=stream:http), reverse_proxy_or_waf_http_logs
  • Severity: high
  • Confidence: high

Splunk SPL

index=network sourcetype="stream:http" http_method IN ("POST","PUT") earliest=-24h
| eval payload=lower(urldecode(coalesce(form_data,"")." ".coalesce(uri_query,"")))
| where match(payload,"hostname\W{1,5}[a-z0-9._-]*([;|\x60$\n]|&&)")
| stats count AS requests min(_time) AS first_seen max(_time) AS last_seen values(uri_path) AS uri_paths values(http_user_agent) AS user_agents values(status) AS http_status by src_ip, dest_ip
| eval first_seen=strftime(first_seen,"%F %T"), last_seen=strftime(last_seen,"%F %T"), detection="CVE-2026-20764 Copeland XWEB Pro hostname OS command injection (TL-2026-3583)"

Microsoft KQL

CommonSecurityLog
| where TimeGenerated > ago(24h)
| where RequestMethod in~ ("POST", "PUT")
| extend Payload = tolower(url_decode(strcat(RequestURL, " ", AdditionalExtensions)))
| where Payload matches regex @"hostname\W{1,5}[a-z0-9._-]*([;|`$\n]|&&)"
| project TimeGenerated, DeviceVendor, DeviceProduct, SourceIP, DestinationIP, RequestMethod, RequestURL, RequestClientApplication, Payload

Sigma

title: Copeland XWEB Pro Hostname Field Command Injection (CVE-2026-20764)
id: 7c3a1e52-3583-4f0a-8b61-1d2e9a40b501
status: experimental
description: Detects HTTP requests to a web management interface where the hostname parameter carries shell metacharacters, the injection mechanism of CVE-2026-20764 in Copeland XWEB Pro 1.12.1 and prior.
references:
    - https://www.cisa.gov/news-events/ics-advisories/icsa-26-057-10
    - https://nvd.nist.gov/vuln/detail/CVE-2026-20764
    - https://it.claroty.com/team82/disclosure-dashboard/cve-2026-20764
author: Threadlinqs Team
date: 2026-10-15
tags:
    - attack.initial_access
    - attack.t1190
    - attack.execution
    - attack.t1059.004
    - cve.2026.20764
logsource:
    category: webserver
detection:
    selection:
        cs-method:
            - POST
            - PUT
            - GET
        cs-uri-query|re: '(?i)hostname\W{1,5}[a-z0-9._-]*(;|\||`|\$|%3b|%7c|%60|%24|%0a|&&|%26%26)'
    condition: selection
falsepositives:
    - Administrators setting an unusual but legitimate hostname through a scripted API client
    - Vulnerability scanners or red-team exercises testing CWE-78 against XWEB Pro
level: high

Known false positives:

  • Authorized vulnerability scanning or red-team tests of the XWEB Pro hostname field
  • Admin automation posting form bodies where a hostname value is immediately followed by a semicolon or pipe

Tuning notes: Requires HTTP request-body visibility (Splunk Stream, WAF body logging or a TLS-terminating reverse proxy); URI-only logs catch query-string abuse only. Scope dest_ip to XWEB Pro management addresses if the index is large. Alert on any match from a non-admin source and pair with SPL-002 to confirm command execution.

8 more detection rules (Splunk SPL, Microsoft KQL, Sigma) · unlock with TL Creds. Sign up free to unlock the detection rules or query them with the Threadlinqs MCP server (Purple)
  • XWEB Pro Sibling CWE-78 Injection — Import Preconfiguration and OpenSSL Utility Routes · unlock with TL Creds
  • Hostname Command Line Carrying Shell Metacharacters (XWEB Pro Setup Injection) · unlock with TL Creds
  • XWEB Pro Controller Recurring Connections to Non-Allowlisted External Hosts · unlock with TL Creds
  • Internet-Sourced Configuration Requests to Copeland XWEB Pro Management Interface · unlock with TL Creds
  • Persistence Paths Written by Management Service or Downloader (Post-Exploitation of XWEB Pro) · unlock with TL Creds
  • Reverse-Shell Style Outbound Connection by Netcat-Like Tool on Linux Controller · unlock with TL Creds
  • XWEB Pro Management Service Spawning Shell or Download Utility After Hostname Change · unlock with TL Creds
  • XWEB Pro Device Fetching Payloads with wget/curl/Busybox to Non-Vendor Hosts · unlock with TL Creds

Indicators of compromise

As of 2026-10-15, Threadlinqs Intelligence tracks 8 indicators of compromise for TL-2026-3583.

8 indicators of compromise · unlock with TL Creds. Compare plans

Technical analysis

CVE-2026-20764 is an OS command injection vulnerability in the web management platform of Copeland XWEB Pro, a refrigeration/HVAC monitoring and control product used in commercial facilities. Per the CVE record published by CISA (ICS-CERT CNA), XWEB Pro version 1.12.1 and prior is affected: an authenticated attacker can supply malicious input through the device hostname configuration, and that value is later processed during system setup, resulting in execution of attacker-controlled operating system commands on the device.

The flaw is one of 23 vulnerabilities in XWEB and XWEB Pro disclosed together in CISA advisory ICSA-26-057-10 (published 2026-02-26) and credited to Amir Zaltzman and Noam Moshe of Claroty Team82. 20 of the 23 are CWE-78 command injections in different features (examples named by Team82: the server username field of the import-preconfiguration action in the API V1 route, CVE-2026-23702; OpenSSL argument fields in the utility route, CVE-2026-24695). The advisory also lists higher-severity siblings, including CVE-2026-21718 (CVSS 10.0, broken cryptography), CVE-2026-24663 (CVSS 9.0, command injection) and CVE-2026-25085 (CVSS 8.6). CISA summarizes the combined impact as authentication bypass, denial of service, memory corruption and arbitrary code execution. Chaining an authentication-bypass sibling with this authenticated injection would raise practical risk, but that chain is not described in the cited sources.

Scoring differs by source: the CISA CNA vector is CVSS:3.1/AV:N/AC:H/PR:H/UI:N/S:C/C:H/I:H/A:H (8.0 HIGH), while the NVD primary score is 8.8 HIGH (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H). The exploit requires valid credentials and network reach to the XWEB Pro management interface. No public proof-of-concept and no in-the-wild exploitation are reported (CISA). The sources publish no network indicators, hashes or malware; defensible indicators are behavioral (shell metacharacters in the hostname field and anomalous child processes spawned by the management service).

Copeland has provided a fix. Users should update XWEB Pro to the latest version from the Copeland software update page, or, on an internet-connected device, via SYSTEM > Updates | Network. CISA recommends minimizing network exposure of control systems, placing them behind firewalls isolated from business networks, and using VPNs for remote access.

MITRE ATT&CK techniques by tactic:

Execution

T1059 Command and Scripting Interpreter

Initial Access

T1078 Valid Accounts; T1190 Exploit Public-Facing Application

Persistence

T1078 Valid Accounts

Privilege Escalation

T1078 Valid Accounts

Remediation

Patches

  • Update XWEB Pro to the latest version from https://webapps.copeland.com/Dixell/Pages/SystemSoftwareUpdate
  • Internet-connected units can update from Copeland servers via SYSTEM > Updates | Network

Immediate actions

  • Identify all Copeland XWEB 300D PRO, 500D PRO and 500B PRO units running firmware 1.12.1 or earlier
  • Remove XWEB Pro management interfaces from direct internet exposure
  • Audit and rotate XWEB Pro administrator and user credentials, since exploitation requires authentication
  • Review device hostname settings for shell metacharacters or unexpected values

Workarounds

  • Restrict management-interface access to trusted administrator hosts until patched
  • Limit the number of accounts that can change device configuration

Longer-term hardening

  • Place control systems behind firewalls isolated from business networks
  • Use VPNs with MFA for any required remote access
  • Apply defense-in-depth and monitor management-interface traffic and configuration changes

Affected and fixed versions

  • Copeland — XWEB 300D PRO
    Vulnerable versions: <=1.12.1
    Fixed in: Latest XWEB Pro release per Copeland software update page
  • Copeland — XWEB 500D PRO
    Vulnerable versions: <=1.12.1
    Fixed in: Latest XWEB Pro release per Copeland software update page
  • Copeland — XWEB 500B PRO
    Vulnerable versions: <=1.12.1
    Fixed in: Latest XWEB Pro release per Copeland software update page

Timeline

  • CVE-2026-20764 reserved by CISA as ICS-CERT CNA
  • CISA states no known public exploitation of these vulnerabilities had been reported to it
  • Copeland provides a fix; users directed to the software update page or SYSTEM > Updates | Network
  • CISA publishes ICSA-26-057-10 covering 23 vulnerabilities in Copeland XWEB and XWEB Pro, credited to Claroty Team82 researchers
  • CVE-2026-20764 published with CWE-78 and CVSS 3.1 score 8.0 from the CNA
  • NVD record last modified; NVD primary score listed as 8.8 HIGH alongside the CNA score of 8.0

Sources cited

Other reports on CVE-2026-20764

Previous and next in vulnerability

Drafted by the Threadlinqs research pipeline from 9 sources; published ; last updated —.