Threat reportVulnerabilityTL-2026-3888
Claroty Team82: AI coding agent (Claude Sonnet 4.6 via Cursor) reproduces Danfoss AK-SM 800A exploits (CVE-2025-41450, CVE-2025-41451, CVE-2025-41452), chaining auth bypass and command injection for root command execution in ~28 minutes
Claroty Team82 ran an AI coding agent in a researcher-guided lab exercise to reproduce three previously disclosed Danfoss AK-SM 800A refrigeration-controller vulnerabilities and chained the authentication bypass with the command injection to demonstrate root-level command execution in about 28 minutes for roughly $6 of AI usage.
Key facts
| Identifiers | TL-2026-3888, CVE-2025-41450, CVE-2025-41451, CVE-2025-41452 |
|---|---|
| Also known as | Freeze the Controller, Defrost the Food, Danfoss AK-SM code-of-the-day bypass |
| Severity | HIGH |
| CVSS | 8.2 (CVSS:3.1/AV:N/AC:H/PR:N/UI:R/S:C/C:H/I:L/A:H) |
| Exploitation status | Public proof-of-concept exploit for a linked CVE |
| EPSS | CVE-2025-41451: 4.4% (91.4th percentile); CVE-2025-41450: 0.9% (61.2th percentile); CVE-2025-41452: 0.9% (60.4th percentile) |
| Affected products | Danfoss AK-SM 8xxA Series (AK-SM 800A) |
| Weaknesses (CWE) | CWE-287, CWE-77, CWE-15 |
| Tools | Censys, Claude Sonnet 4.6, Cursor, Ghidra, fromagegate |
| MITRE ATT&CK techniques | T1059.004 Unix Shell, T1190 Exploit Public-Facing Application, T1587.004 Exploits, T1588.005 Exploits, T1595.002 Vulnerability Scanning, T1596.005 Scan Databases |
| Motivation | UNKNOWN |
| Target sectors | retail, food-and-beverage, cold-chain, logistics, industrial-control-systems |
| Target regions | Europe, france, south africa, North America |
| Detection rules | 9 (1 shown free) |
| Sources | 11 cited sources |
Detection coverage
As of 2026-10-19, Threadlinqs Intelligence publishes 9 detection rule(s) for TL-2026-3888 across Splunk SPL, Microsoft KQL and Sigma, covering 8 indicator(s) of compromise. The whole corpus is readable without an account. Every threat comes with one complete detection in Splunk SPL, Microsoft KQL and Sigma, free for everyone; a free account adds daily TL Creds to unlock the rest. Paid plans add a larger daily allowance, correlation and the MCP server. Threadlinqs MCP server · View plans.
Free detection: Danfoss AK-SM Controller Outbound Connection to Internet (Reverse Shell / Tool Download)
Detects an inventoried AK-SM/AK-SC controller initiating allowed outbound connections to public addresses on ports other than DNS, NTP and SMTP. After the CVE-2025-41450 and CVE-2025-41451 chain gives root command execution, a reverse shell, payload download or C2 callback is the expected next step. Controllers normally only talk to local management hosts, time and mail servers, so internet-bound sessions are anomalous. Command execution on a refrigeration controller was reportedly used to drive defrost cycles in the October 2026 French incidents, although the initial access route is unconfirmed.
- Languages: Splunk SPL, Microsoft KQL, Sigma
- ATT&CK: T1071.001, T1105, T1059.004
- Data sources: Network_Traffic datamodel, CommonSecurityLog, firewall
- Severity: high
- Confidence: medium
Splunk SPL
| tstats summariesonly=true count min(_time) AS first_seen max(_time) AS last_seen from datamodel=Network_Traffic.All_Traffic where All_Traffic.action=allowed [| inputlookup ak_sm_controllers.csv | rename ip AS All_Traffic.src | fields All_Traffic.src] by All_Traffic.src All_Traffic.dest All_Traffic.dest_port
| rename All_Traffic.* AS *
| where NOT (cidrmatch("10.0.0.0/8", dest) OR cidrmatch("172.16.0.0/12", dest) OR cidrmatch("192.168.0.0/16", dest))
| where dest_port!=25 AND dest_port!=53 AND dest_port!=123 AND dest_port!=465 AND dest_port!=587
| convert ctime(first_seen) ctime(last_seen)Microsoft KQL
let controllers = _GetWatchlist('AKSMControllers') | project SourceIP = tostring(SearchKey);
CommonSecurityLog
| where TimeGenerated > ago(24h)
| where SourceIP in (controllers)
| where DeviceAction in~ ("allow", "allowed", "accept", "permit")
| where not(ipv4_is_private(DestinationIP))
| where DestinationPort !in (25, 53, 123, 465, 587)
| summarize connections = count(), first_seen = min(TimeGenerated), last_seen = max(TimeGenerated) by SourceIP, DestinationIP, DestinationPort
| project first_seen, last_seen, SourceIP, DestinationIP, DestinationPort, connectionsSigma
title: Danfoss AK-SM Controller Outbound Connection to Public Address
id: b47d0a96-2e5c-4f13-8a7b-1d6e9c3f5a28
status: experimental
description: Detects an AK-SM/AK-SC refrigeration controller initiating an allowed connection to a public address on a non-DNS/NTP/SMTP port, consistent with a reverse shell or payload download after CVE-2025-41451 command injection. Controller hosts are identified by naming convention; adapt to your asset inventory.
references:
- https://www.cisa.gov/news-events/ics-advisories/icsa-25-140-03
author: Threadlinqs Team
date: 2026-10-19
tags:
- attack.command-and-control
- attack.t1071.001
- attack.t1105
- attack.execution
- attack.t1059.004
logsource:
category: firewall
detection:
selection:
action: 'allowed'
src_host|contains:
- 'ak-sm'
- 'aksm'
- 'ak-sc'
filter_private:
dst_ip|cidr:
- '10.0.0.0/8'
- '172.16.0.0/12'
- '192.168.0.0/16'
filter_ports:
dst_port:
- 25
- 53
- 123
- 465
- 587
condition: selection and not filter_private and not filter_ports
falsepositives:
- Controllers configured for vendor cloud, remote service or SNMP/NTP to public servers
level: highKnown false positives:
- Controllers legitimately connecting to a vendor cloud or remote-monitoring service on 443
- Maintenance firms using a reverse tunnel for remote support
Tuning notes: Maintain ak_sm_controllers.csv (column ip) and the AKSMControllers Sentinel watchlist (SearchKey = IP) from your asset inventory; the Sigma rule uses hostname convention instead and needs adapting. Allow-list sanctioned vendor or monitoring destinations. For fleets that must reach a cloud service on 443, restrict the rule to destinations outside that allow-list rather than dropping it. This detection is inferred from the exploit's root command execution capability; no C2 infrastructure has been published.
- Danfoss AK-SM Email/Alarm-to-Mail Settings Request with Shell Metacharacters (CVE-2025-41451) · unlock with TL Creds
- Danfoss AK-SM load_nginx_headers Endpoint Use (CVE-2025-41452 Nginx Config Injection / DoS) · unlock with TL Creds
- Danfoss AK-SM [indicator] Sweep Across Multiple Controllers from One Source · unlock with TL Creds
- Danfoss AK-SM Management Interface Reachable from Internet · unlock with TL Creds
- Danfoss AK-SM Web Application Writing Nginx Configuration (CVE-2025-41452) · unlock with TL Creds
- Ghidra Analysis of Danfoss AK-SM Firmware Binaries on Corporate Endpoint (Exploit Development Indicator) · unlock with TL Creds
- Danfoss AK-SM [indicator] getauth Abuse from External Source (CVE-2025-41450 Code-of-the-Day Bypass) · unlock with TL Creds
- Danfoss AK-SM sm_app / sm_fcgi_app Spawning Shell with Injection Indicators (CVE-2025-41451) · unlock with TL Creds
Indicators of compromise
As of 2026-10-19, Threadlinqs Intelligence tracks 8 indicators of compromise for TL-2026-3888.
Technical analysis
It was a reproduction of known, patched flaws, not new discovery, but it shows how cheaply AI can accelerate exploit development against internet-exposed OT; Claroty states the route used in the October 2026 French supermarket refrigeration attacks has not been established.
Danfoss AK-SM 800A is a centralized refrigeration management platform used in supermarkets, cold-storage facilities and warehouses. Its embedded web management interface sits behind an externally exposed Nginx reverse proxy that forwards to sm_fcgi_app, then an internal Nginx instance and sm_app (core web application, Task_Web). Authentication flows through xml.cgi with a getauth action routed to handler functions.
Claroty Team82 (researcher Tomer Goldschmidt) previously disclosed three vulnerabilities in this interface, documented in CISA ICSA-25-140-03: CVE-2025-41450 (CWE-287, CVSS v3.1 8.2) is a hidden 'code-of-the-day' authentication path, activated by specific request parameters, that validates against a time-based code derived from the device date/time (check_code_of_day), letting an attacker who reproduces the algorithm obtain an administrative session without knowing the password; fixed in R4.2. CVE-2025-41451 (CWE-77, CVSS v3.1 7.6) is an OS command injection where the unsanitized email/alarm-to-mail SMTP authentication password field is formatted into a shell command, giving post-authentication RCE; fixed in R4.3.1. CVE-2025-41452 (CWE-15, CVSS v3.1 5.4) lets an authenticated user upload arbitrary Nginx configuration directives through the load_nginx_headers endpoint, enabling routing manipulation of the internet-facing Nginx and denial of service via unhandled exceptions/process crashes; fixed in R4.3.1. Claroty's Censys scan found 2,765 exposed AK-SM 800A devices.
In the AI exercise (reported 2026-10-13), Claroty ran Claude Sonnet 4.6 in medium reasoning mode through the Cursor AI coding editor against a Danfoss AK-SM 800A in a laboratory. Inputs were public vulnerability information, firmware downloaded from Danfoss's website and analysis tooling. About 28 minutes elapsed from initial analysis to a working exploit; AI usage was estimated at about $6. The agent reproduced two vulnerabilities initially; researchers redirected the authentication-bypass analysis when it went off track and supplied Ghidra integration for the roughly 67 MB binary, after which the agent chained the authentication bypass with the command injection to demonstrate root-level command execution on the lab device. Claroty stresses this was a researcher-guided reproduction of known flaws, not discovery of new vulnerabilities.
Context: on the night of 2026-10-11 attackers remotely drove cold-storage defrost cycles at French retailers (temperatures reported near 50C); CERT-FR named Danfoss AK-SM and AK-SC and Copeland/Dixell xweb controllers and cited numerous compromises without naming a vulnerability, and Danfoss said most affected units were end-of-life (notably AK-SM800 and AK-SC355) with some AK-SM800A units on outdated firmware. Reported scale varies by source (roughly 250-350, over 400, up to about 700 stores). No source ties the incident to these CVEs or to AI-assisted tooling; initial access is unconfirmed, no actor has been attributed, and no network IOCs were published. Third-party exposure counts (4,980 hosts, about 58% in France, per cybersecuritynews) reflect Shodan exposure, not confirmed compromise. A third-party public PoC ('fromagegate') reconstructing a suspected chain was reported on social media; its content was not independently verified. Severity reflects the highest component CVSS (8.2) and the chained pre-auth-to-root outcome.
MITRE ATT&CK techniques by tactic:
Execution
Initial Access
T1190 Exploit Public-Facing Application
Resource Development
T1587.004 Exploits; T1588.005 Exploits
Reconnaissance
Remediation
Patches
- Danfoss AK-SM 8xxA firmware R4.2 (CVE-2025-41450)
- Danfoss AK-SM 8xxA firmware R4.3.1 (CVE-2025-41451, CVE-2025-41452)
Immediate actions
- Upgrade Danfoss AK-SM 8xxA firmware to R4.3.1 or later (R4.2 fixes only CVE-2025-41450)
- Remove or filter internet exposure of AK-SM/AK-SC and xweb controller management interfaces
- Review controllers for unexpected admin sessions, email/alarm-to-mail settings changes and uploaded Nginx header configuration
- Treat end-of-life units (e.g. AK-SM800, AK-SC355) as compromised-if-exposed; a factory reset alone is reportedly not sufficient per CERT-FR
Workarounds
- Firewall/ACL the web management interface so it is not reachable from the internet
- Require VPN for remote access by maintenance firms
- Monitor web requests to xml.cgi getauth, email configuration and load_nginx_headers endpoints
Longer-term hardening
- Restrict administrative access to trusted management networks or VPNs
- Implement network segmentation between OT and business networks
- Replace end-of-life controllers that no longer receive security updates
- Assume AI-assisted exploit development shortens the patch-to-exploit window for internet-facing OT and prioritise patching accordingly
Affected and fixed versions
- Danfoss — AK-SM 8xxA Series (AK-SM 800A)
Vulnerable versions: CVE-2025-41450: versions prior to R4.2; CVE-2025-41451 and CVE-2025-41452: versions prior to 4.3.1
Fixed in: R4.2 (CVE-2025-41450); R4.3.1 or later (all three CVEs)
Timeline
- CISA publishes ICSA-25-140-03 for Danfoss AK-SM 8xxA covering CVE-2025-41450, CVE-2025-41451 and CVE-2025-41452, crediting Tomer Goldschmidt of Claroty Team82
- CISA releases Update A to ICSA-25-140-03; Danfoss fixes are R4.2 (CVE-2025-41450) and R4.3.1 (CVE-2025-41451/41452)
- Claroty Team82 publishes 'Freeze the Controller, Defrost the Food' detailing the three AK-SM 800A flaws and 2,765 Censys-visible exposed devices
- Overnight, attackers remotely trigger defrost cycles on refrigeration controllers at French supermarkets, with reported temperatures near 50C; initial access vector not confirmed
- CERT-FR alert names Danfoss AK-SM/AK-SC and Copeland/Dixell xweb controllers and cites numerous compromises without identifying a vulnerability; updated 2026-10-13
- cybersecuritynews reports 4,980 internet-facing Danfoss-related hosts (about 58% in France) based on Shodan exposure, not confirmed compromise
- Claroty reports Claude Sonnet 4.6 via Cursor reproduced the Danfoss flaws in ~28 minutes (~$6) and chained auth bypass with command injection for root command execution on a lab device; route used in French attacks stated as not established
- Briefing update: Danfoss states most affected units are end-of-life (notably AK-SM800 and AK-SC355) and no link to the Claroty flaws is established
Sources cited
- CISA ICS Advisory ICSA-25-140-03 - Danfoss AK-SM 8xxA Series (Update A) CISA · Government advisory · 2025-05-20
- Claroty Team82 - Freeze the Controller, Defrost the Food: Uncovering Vulnerabilities in Danfoss Refrigeration Controllers claroty.com · Research · 2026-08-09
- French supermarkets refrigeration attack: Danfoss says most units end-of-life, no link to Claroty flaws pk-sharma.com · Research · 2026-10-15
- CISO Daily Briefing 2026-10-13 (Cloud Security Alliance Labs) labs.cloudsecurityalliance.org · Research · 2026-10-13
- Claroty Team82 Disclosure Dashboard - CVE-2025-41451 claroty.com · Research
- Claroty Team82 Disclosure Dashboard - CVE-2025-41450 blog.claroty.com · Research
- Claroty says Claude reproduced Danfoss flaws in about 28 minutes (NeoTeo) neoteo.com · News · 2026-10-13
- Industrial Cyber - Claroty Team82 shows AI can rebuild Danfoss controller exploits in 28 minutes industrialcyber.co · News
- Cybernews - Hackers could disable your local supermarket fridge for just $6 cybernews.com · News
- Danfoss Refrigeration Hack Update - 4,980 Hosts Found Exposed to Internet cybersecuritynews.com · News · 2026-10-13
- Refindustry - Danfoss, Copeland and Trane address controller security vulnerabilities refindustry.com · News
Other reports on CVE-2025-41450
- Malicious Cyber Activity Targeting Industrial Refrigeration and Cold Chain Monitoring Systems (Danfoss StoreView, Copeland/Dixell XWEB, Coolworld)
- Second Wave of Attacks on European Supermarket Refrigeration Controllers (Danfoss AK-SM/AK-SC, Copeland/Dixell XWEB) Forces Defrost Mode
- Refrigeration controller attack in France: internet-exposed Danfoss AK-SM/AK-SC and Copeland/Dixell XWEB controllers forced into defrost cycles at hundreds of grocery stores (CVE-2025-41450)
Previous and next in vulnerability
- Threat actor abuses Flowise GenAI orchestration platform (CVE-2025-59528, CVE-2026-41264, CVE-2024-31621 class) and weaponizes its LLM agent for offensive reconnaissance Previous report
- Webmin password_change.cgi Backdoor Remote Code Execution (CVE-2019-15107) - DefCon Zero-Day Disclosure, TCP/10000 Scanning and Roboto P2P Botnet Exploitation Next report
Drafted by the Threadlinqs research pipeline from 11 sources; published ; last updated —.