Threat reportICS/SCADATL-2026-4346

CVE-2025-13902: Stored/Reflected XSS (CWE-79) in Schneider Electric Modicon M241/M251/M258/LMC058 Controllers Web Server

mediumMONITORING

CVE-2025-13902 (TL-2026-4346), also tracked as SEVD-2026-069-01, is a medium-severity ICS/SCADA threat scored CVSS 5.4, first published 2026-10-24. It has no confirmed attribution, affects Schneider Electric Modicon M241 / M251 Controllers, references 2 CVEs (CVE-2025-13902, CVE-2025-13901), maps to 5 MITRE ATT&CK techniques (T1059.007, T1078, T1185), and is covered by 9 detection rules and 9 indicators of compromise.

CVSS
5.4/10Medium
CVEs
2Referenced vulnerabilities
Techniques
5MITRE ATT&CK
Actors
0Not attributed
Detection rules
9SPL · KQL · Sigma
IOCs
9Indicators of compromise

Key facts for TL-2026-4346

Threat ID
TL-2026-4346
Also known as
SEVD-2026-069-01, SEVD-2026-069-02
Severity
MEDIUM
CVSS
5.4 (CVSS:3.1/AV:N/AC:L/PR:L/UI:R/S:C/C:L/I:L/A:N)
Status
MONITORING
Category
ICS_SCADA
First published
Last reviewed
Attribution confidence
LOW
Motivation
UNKNOWN
Target sectors
manufacturing, energy, industrial control systems, critical infrastructure
Target regions
Global
Detection rules
9
Indicators of compromise
9

Malware and tooling in CVE-2025-13902

Malware and tooling: EcoStruxure Machine Expert

How CVE-2025-13902 works

CVE-2025-13902 is a cross-site scripting flaw (CWE-79) in the embedded web server of Schneider Electric Modicon M241/M251 (and M258/LMC058) PLCs, disclosed by Claroty Team82 and covered by Schneider Electric security notice SEVD-2026-069. An authenticated attacker can plant a crafted element that runs arbitrary JavaScript in a victim's browser when they hover over it (CVSS 3.1 5.4 Medium). No in-the-wild exploitation or public PoC is stated in any source.

CVE-2025-13902 is an Improper Neutralization of Input During Web Page Generation (CWE-79) vulnerability in the web server of Schneider Electric Modicon controllers. Per the CVE record and NVD, an authenticated attacker can inject content so that a victim's browser executes arbitrary JavaScript when the victim hovers over a maliciously crafted element hosted on the affected web server. The CVE was reserved on 2025-12-02 and published on 2026-03-10; NVD was last modified on 2026-06-23.

Scoring: NVD lists CVSS 3.1 5.4 MEDIUM (CVSS:3.1/AV:N/AC:L/PR:L/UI:R/S:C/C:L/I:L/A:N) and CVSS 4.0 5.1 MEDIUM (CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:P/VC:N/VI:N/VA:N/SC:L/SI:L/SA:N). The attack is network-reachable and low complexity, but requires low privileges (a valid account on the controller web server) and user interaction (the victim must hover over the crafted element). Scope is changed because the script executes in the victim's browser context rather than on the controller, with limited confidentiality and integrity impact and no availability impact.

Affected products according to the CVE record/NVD: Modicon M241 and M251 firmware prior to 5.4.13.12, and Modicon M258 and LMC058 (all versions). The Claroty Team82 disclosure dashboard and the hunt skeleton name the M241/M251/M262 family; the CVE record does not list the M262 for this CVE, so M262 exposure should be confirmed against the vendor notice. Note also that the CVE record references SEVD-2026-069-02 while the Claroty page links SEVD-2026-069-01; the sibling vulnerability CVE-2025-13901 (CWE-404 partial denial of service over the Machine Expert protocol, CVSS 5.3) is covered by CISA ICSA-26-078-01 (released 2026-03-19) for M241/M251 before 5.4.13.12 and M262 before 5.4.10.12. The vendor PDFs could not be parsed as text during research, so fix and mitigation specifics beyond the version threshold are not independently confirmed.

Defensive relevance: although the XSS itself is Medium severity, it targets the engineering/HMI-style web interface of widely deployed PLCs. Exploitation would let an attacker with a low-privilege account pivot into an operator's or engineer's browser session. Exposure is reduced where controller web servers are not reachable from untrusted networks. No threat actor, malware, C2 infrastructure, exploitation in the wild, CISA KEV listing or public PoC is reported in the sources consulted.

MITRE ATT&CK techniques used in TL-2026-4346

Execution

T1059.007 Command and Scripting Interpreter: JavaScript; T1204 User Execution

Initial Access

T1078 Valid Accounts; T1190 Exploit Public-Facing Application

Collection

T1185 Browser Session Hijacking

Affected products and versions in CVE-2025-13902

  • Schneider Electric — Modicon M241 / M251 Controllers
    Vulnerable versions: prior to 5.4.13.12
    Fixed in: 5.4.13.12
  • Schneider Electric — Modicon M258 / LMC058 Controllers
    Vulnerable versions: all versions
  • Schneider Electric — Modicon M262 Controllers (named in Team82 disclosure; not listed in CVE record for this CVE)
    Vulnerable versions: unconfirmed

Remediation for CVE-2025-13902

Patches

  • Modicon M241/M251: update to firmware 5.4.13.12 or later via EcoStruxure Machine Expert per Schneider Electric notice SEVD-2026-069

Immediate actions

  • Identify Modicon M241/M251 (firmware prior to 5.4.13.12) and M258/LMC058 controllers and restrict access to their web servers to trusted engineering networks only
  • Review and minimize which accounts have access to the controller web server; rotate credentials for any shared or default accounts
  • Avoid browsing controller web pages from the same browser profile used for other sensitive sessions

Workarounds

  • Modicon M258/LMC058: all versions are listed as affected in the CVE record; no fixed version is stated in the sources reviewed, so apply the mitigations in the Schneider Electric notice and network isolation

Longer-term hardening

  • Segment control networks and keep PLC web interfaces off the internet and corporate networks, behind firewalls and VPN for remote access
  • Monitor HTTP requests to controller web servers for script content or unusual parameters

CVEs associated with CVE-2025-13902

CVE-2025-13902, CVE-2025-13901

Weaknesses (CWE) in CVE-2025-13902

CWE-79

Timeline of CVE-2025-13902

  • CVE-2025-13902 reserved (CVE record)
  • Firmware 5.4.13.12 is the first non-vulnerable version for Modicon M241/M251; M258/LMC058 listed as all versions affected
  • Sibling Modicon vulnerability CVE-2025-13901 (CWE-404 partial DoS over Machine Expert protocol, CVSS 5.3) published the same day
  • CVE-2025-13902 published; Schneider Electric security notice SEVD-2026-069 released for Modicon M241/M251 and M258/LMC058 (CWE-79 XSS, CVSS 5.4)
  • CISA releases ICSA-26-078-01 for Modicon M241/M251/M262 covering CVE-2025-13901 (credits Claroty Team82); it does not mention CVE-2025-13902
  • NVD record for CVE-2025-13902 last modified with CVSS 3.1 5.4 and CVSS 4.0 5.1 scoring

Sources cited for CVE-2025-13902

Detection coverage for TL-2026-4346

As of 2026-10-24, Threadlinqs Intelligence publishes 9 detection rule(s) for TL-2026-4346 across Splunk SPL, Microsoft KQL and Sigma, covering 9 indicator(s) of compromise. The whole corpus is readable without an account; a free account unlocks full detection query text in Splunk SPL, Microsoft KQL and Sigma; paid tiers add raw indicator values, correlation and the MCP server. Threadlinqs MCP server · View plans.

9 detection rules (Splunk SPL, Microsoft KQL, Sigma) · Blue and above. Compare plans
9 indicators of compromise · Red and above. Compare plans