# US Water Sector Supply-Chain Exposure: Unreported Exploited ICS Vulnerabilities and Internet-Exposed PLCs/Cellular Modems Targeted by Iranian-Affiliated Actors (Securin Water Supply Chain Watch, CISA AA26-097A)

> Securin's Water Supply Chain Watch index of 236 vendors serving US water and wastewater systems found almost twice as many vulnerabilities as public records, including 20 exploited flaws absent from CISA KEV. Real-world intrusions, including July 2026 activity against 100+ internet-exposed water systems and the Iranian-affiliated PLC campaign in CISA AA26-097A, rely mainly on exposed controllers behind cellular modems and default or missing credentials rather than software bugs.

- **Published:** 2026-11-25T19:56:28Z
- **Last reviewed:** 2026-11-25T19:56:28Z
- **Canonical:** https://intel.threadlinqs.com/threat/TL-2026-6885
- **Card image:** https://intel.threadlinqs.com/og/threat/TL-2026-6885.png
- **ID:** TL-2026-6885
- **Severity:** HIGH
- **Category:** ICS_SCADA
- **Status:** ACTIVE
- **Actor:** Iranian-affiliated APT actors (Iran)
- **Detections:** 9 (1 shown free below) · **IOCs:** 25 (3 shown free below)
- **CVEs:** CVE-2017-16740

## Description

Securin's Water Supply Chain Watch (reported by The Register on 2026-11-25) examined 236 technology vendors supplying US drinking water, wastewater and industrial water systems, comparing CISA, EPA, FBI and WaterISAC data (CISA advisory data through 2026-11-20, KEV entries through 2026-11-23). The federal government has issued 4,014 ICS security advisories and cataloged 1,792 known-exploited vulnerabilities; Securin's index found almost twice as many vulnerabilities as public records identified, including 20 exploited flaws that are not in CISA KEV. Federal water advisories reached their highest level this year since 2020. Five vendors account for 191 of 376 water-tagged advisories: Rockwell Automation (58), Advantech (48), Schneider Electric (35), Siemens (26) and ABB (24). Advantech had the most critical-rated vulnerabilities but none appear in KEV. Securin notes that advisory volume is not a reliable predictor of attacks: Unitronics had only 2 water-tagged advisories, yet at least 75 of its controllers were compromised between November 2023 and January 2024 through default or missing passwords.

Exposure is the dominant risk. Securin counted 791 Rockwell MicroLogix 1400 controllers across US industries exposed to the internet as of 2026-11-17. Forescout research (August 2026 scan) reported 4,407 exposed Rockwell controllers worldwide, 2,844 in the US, with about 70% of US-based devices in large mobile carrier networks reached via cellular routers; 22 internet-facing Rockwell PLCs were found in cities hit by recent water-utility attacks, 19 of them on the same carrier network, and 19 of the 22 ran firmware susceptible to CVE-2017-16740 (Modbus TCP buffer overflow). Forescout could not confirm those specific devices were compromised and stated the publicly described effects could be achieved without an exploit, because attackers can change IP addresses and passwords on reachable controllers. Poorly secured cellular modems, often installed by third-party contractors and undocumented, are a recurring entry point.

CISA, FBI, NSA, EPA, DOE, CNMF and Treasury advisory AA26-097A (published 2026-04-07, updated 2026-07-22) describes Iranian-affiliated APT actors accessing internet-facing PLCs (Rockwell/Allen-Bradley CompactLogix and Micro850, Schneider Electric BMX P34/Modicon M340, Siemens S7-1200, and potentially any exposed PLC) from foreign-based and leased third-party hosted IP addresses, using the vendors' own programming software (Studio 5000 Logix Designer, EcoStruxure Control Expert, TIA Portal) on ports 44818, 2222, 102 and 502, with Dropbear SSH on victim cellular modems over port 22. Actors downloaded project files, exfiltrated them over third-party hosted infrastructure, and at one victim uploaded a malicious project that preserved downstream ladder logic but overrode logic maintaining safe operating parameters, disabling shutdown and alarm logic; HMI/SCADA displays were also altered. Activity has been ongoing since at least March 2026, with operational disruption and financial loss at some victims in government services, water/wastewater and energy. In July 2026 CISA reported malicious activity against over 100 internet-exposed WWS systems, commonly PLCs connected directly to a cellular modem, in at least 12 states (Minnesota, Michigan, Georgia, South Dakota and New Jersey named in press), mostly small rural utilities. Press and third-party analysts suspect Iran (CyberAv3ngers named in Register coverage); the federal government had not formally attributed the July activity to a named group. No CVEs are the primary vector; Securin and the source article contain no malware names or hashes. Severity is analyst-assigned.

## MITRE ATT&CK

- T1219 Remote Access Tools
- T1565 Data Manipulation

## Free detection (Splunk SPL, Microsoft KQL, Sigma)

**AA26-097A Internet-Sourced Access to PLC Ports (EtherNet/IP, S7comm, Modbus) — Exploitation** (`TL-2026-6885-SPL-001`)

Flags allowed sessions from non-RFC1918 sources to TCP 44818, 2222, 102 and 502 and tags matches to AA26-097A actor IPs. Reflects TL-2026-6885 behaviour where Iranian-affiliated actors reach internet-exposed Rockwell, Schneider and Siemens PLCs, often behind cellular modems with default or missing credentials; also surfaces exposure to CVE-2017-16740 (Modbus/TCP buffer overflow).

- **Languages:** Splunk SPL, Microsoft KQL, Sigma
- **ATT&CK:** T1190, T1133, T1078.001
- **Data sources:** pan:traffic, firewall
- **Severity:** high
- **Confidence:** high

### Splunk SPL

```spl
index=firewall sourcetype="pan:traffic" action=allowed dest_port IN (44818,2222,102,502) earliest=-24h | where NOT (cidrmatch("10.0.0.0/8",src_ip) OR cidrmatch("172.16.0.0/12",src_ip) OR cidrmatch("192.168.0.0/16",src_ip)) | eval aa26_097a_ioc=if(in(src_ip,"185.82.73.175","141.11.164.153","175.110.121.42","175.110.121.39","175.110.121.41","175.110.121.107","192.142.54.79","84.200.205.165","185.225.17.225","79.133.46.209","88.80.150.199","88.80.150.200","88.80.150.202","185.82.73.162","185.82.73.164","185.82.73.165","185.82.73.167","185.82.73.168","185.82.73.170","185.82.73.171","135.136.1.133"),1,0), ics_protocol=case(dest_port=44818 OR dest_port=2222,"EtherNet/IP-CIP",dest_port=102,"S7comm",dest_port=502,"Modbus/TCP",true(),"other") | stats count AS sessions sum(bytes_out) AS bytes_to_plc sum(bytes_in) AS bytes_from_plc dc(dest_ip) AS plcs_touched values(dest_ip) AS plc_targets values(ics_protocol) AS protocols max(aa26_097a_ioc) AS ioc_hit min(_time) AS first_seen max(_time) AS last_seen by src_ip dest_port | eval threat="TL-2026-6885 AA26-097A internet-to-PLC access (T1190/T1133/T1078.001; CVE-2017-16740 Modbus/502 exposure)" | convert ctime(first_seen) ctime(last_seen) | sort - ioc_hit - sessions
```

### Microsoft KQL

```kql
let aa26_097a_iocs = dynamic(['185.82.73.175', '141.11.164.153', '175.110.121.42', '175.110.121.39', '175.110.121.41', '175.110.121.107', '192.142.54.79', '84.200.205.165', '185.225.17.225', '79.133.46.209', '88.80.150.199', '88.80.150.200', '88.80.150.202', '185.82.73.162', '185.82.73.164', '185.82.73.165', '185.82.73.167', '185.82.73.168', '185.82.73.170', '185.82.73.171', '135.136.1.133']);
CommonSecurityLog
| where TimeGenerated > ago(24h)
| where DeviceAction in~ ('allow', 'accept', 'allowed', 'permit')
| where DestinationPort in (44818, 2222, 102, 502)
| where not(ipv4_is_private(SourceIP))
| extend IocMatch = SourceIP in (aa26_097a_iocs),
    IcsProtocol = case(DestinationPort in (44818, 2222), 'EtherNet/IP-CIP', DestinationPort == 102, 'S7comm', DestinationPort == 502, 'Modbus/TCP', 'other')
| summarize Sessions = count(), PlcTargets = make_set(DestinationIP, 50), FirstSeen = min(TimeGenerated), LastSeen = max(TimeGenerated), IocHit = max(toint(IocMatch)) by SourceIP, DestinationPort, IcsProtocol, DeviceVendor
| project FirstSeen, LastSeen, SourceIP, DestinationPort, IcsProtocol, Sessions, PlcTargets, IocHit, DeviceVendor
| order by IocHit desc, Sessions desc
```

### Sigma

```yaml
title: Internet-Sourced Access to PLC Ports or AA26-097A Actor IP (TL-2026-6885)
id: 6a1f3c52-8d47-4b9e-a2c1-5e0b7d914a01
status: experimental
description: Detects allowed firewall sessions from non-RFC1918 sources to PLC protocol ports 44818, 2222, 102 and 502 (EtherNet/IP, S7comm, Modbus/TCP), or any session from AA26-097A actor-associated IPs. Matches the exposed-PLC access pattern used by Iranian-affiliated actors against water systems and the exposure relevant to CVE-2017-16740.
references:
    - https://www.cisa.gov/news-events/cybersecurity-advisories/aa26-097a
    - https://www.forescout.com/blog/ot-security-analysis-exposed-devices-attacked-in-us-water-systems/
    - https://www.securin.io/reports/water-supply-chain-watch
author: Threadlinqs Team
date: 2026/11/25
tags:
    - attack.initial-access
    - attack.t1190
    - attack.t1133
    - attack.persistence
    - attack.t1078.001
    - cve.2017.16740
logsource:
    category: firewall
detection:
    selection_ports:
        dst_port: [44818, 2222, 102, 502]
    filter_internal_src:
        src_ip|cidr: ['10.0.0.0/8', '172.16.0.0/12', '192.168.0.0/16']
    selection_ioc:
        src_ip: ['185.82.73.175', '141.11.164.153', '175.110.121.42', '175.110.121.39', '175.110.121.41', '175.110.121.107', '192.142.54.79', '84.200.205.165', '185.225.17.225', '79.133.46.209', '88.80.150.199', '88.80.150.200', '88.80.150.202', '185.82.73.162', '185.82.73.164', '185.82.73.165', '185.82.73.167', '185.82.73.168', '185.82.73.170', '185.82.73.171', '135.136.1.133']
    condition: (selection_ports and not filter_internal_src) or selection_ioc
falsepositives:
    - Authorized remote vendor support or integrator access to PLCs
    - Cloud or MSSP monitoring platforms polling OT assets
level: high

```

**Known false positives:**

- Authorized vendor or integrator remote support reaching PLCs from public addresses
- Managed-service or SCADA hosting providers polling OT sites through carrier NAT

**Tuning notes:** Add known vendor and integrator source IPs to an allowlist; adjust index/sourcetype and field names (src_ip, dest_port, bytes_out) to your firewall; refresh the AA26-097A IP list from the CISA STIX feed and vet before blocking.

### 8 more detection rules (Splunk SPL, Microsoft KQL, Sigma), unlock with TL Creds

- Sentinel: Internet-Sourced Sessions to PLC Ports or AA26-097A IPs — Exploitation (locked: unlock with TL Creds)
- Sentinel: PLC Engineering Software Connecting to Public IP — Post-Exploitation (locked: unlock with TL Creds)
- Sentinel: Dropbear SSH Login from Public IP on Cellular Modem Syslog — C2 / Remote Access (locked: unlock with TL Creds)
- Sigma: Internet-Sourced Access to PLC Ports or AA26-097A IP — Exploitation (locked: unlock with TL Creds)
- Sigma: PLC Engineering Software to Public IP on ICS Ports — Post-Exploitation (locked: unlock with TL Creds)
- Sigma: Dropbear SSH Success Involving AA26-097A Actor IP — C2 / Remote Access (locked: unlock with TL Creds)
- PLC Project Download/Upload or Stop Command from External Source — Post-Exploitation (locked: unlock with TL Creds)
- External SSH to Dropbear Cellular Modem Fronting PLC — C2 / Remote Access (locked: unlock with TL Creds)

Sign up free to unlock the detection rules: https://threadlinqs.com/?modal=signup

## Sample indicators (3 of 25)

Defanged, TLP:CLEAR.

- IP address: `185.82.73[.]175`
- IP address: `141.11.164[.]153`
- IP address: `175.110.121[.]42`

Full set of 25 indicators unlocks with TL Creds: https://threadlinqs.com/tl-creds

## Sources

- [The security of US water systems is even leakier than we thought (The Register)](https://www.theregister.com/security/2026/11/25/the-security-of-us-water-systems-is-even-leakier-than-we-thought/5312243)
- [CISA AA26-097A: Iranian-Affiliated Cyber Actors Exploit Programmable Logic Controllers Across US Critical Infrastructure](https://www.cisa.gov/news-events/cybersecurity-advisories/aa26-097a)
- [Securin Water Supply Chain Watch](https://www.securin.io/reports/water-supply-chain-watch)
- [More than 100 water systems were hit in July cyberattacks (The Register)](https://www.theregister.com/cyber-crime/2026/08/26/more-than-100-water-systems-were-hit-in-july-cyberattacks/5292685)
- [MITRE ATT&CK for ICS T0883 Internet Accessible Device](https://attack.mitre.org/versions/v19/techniques/T0883/)
- [Forescout: OT security analysis of exposed devices attacked in US water systems](https://www.forescout.com/blog/ot-security-analysis-exposed-devices-attacked-in-us-water-systems/)
- [Over 4,400 Rockwell PLCs Exposed Online, 22 Found in Water Attack Cities (The Hacker News)](https://thehackernews.com/2026/08/over-4400-rockwell-plcs-exposed-online.html)
- [Iran-linked CyberAv3ngers suspected in attacks on Minnesota water systems (The Register)](https://www.theregister.com/security/2026/07/29/iran-linked-cyberav3ngers-suspected-in-attacks-on-minnesota-water-systems/5280357)
- [Georgia, Michigan say water systems hacked by Iran-tied crew (The Register)](https://www.theregister.com/security/2026/08/03/georgia-michigan-say-water-systems-hacked-by-iran-tied-crew/5282262)
- [AA26-097A STIX indicators (July 2026)](https://www.cisa.gov/sites/default/files/2026-07/AA26-097A.stix_.json)
- [Water system controllers don't belong on the internet, says ex-NSA chief (The Register)](https://www.theregister.com/security/2026/08/07/water-system-controllers-dont-belong-on-the-internet-says-ex-nsa-chief-after-suspected-iran-attacks/5285070)
- [CISA AA23-335A: Exploitation of Unitronics PLCs used in Water and Wastewater Systems](https://www.cisa.gov/news-events/cybersecurity-advisories/aa23-335a)

## Full data

The other 8 detection rules (Splunk SPL / Microsoft KQL / Sigma) unlock with TL Creds; a free account includes daily creds: https://threadlinqs.com/?modal=signup
Indicator values unlock with TL Creds, at a lower price on Red and Purple; AI agents can query rules and IOCs through the Threadlinqs MCP server (Purple and Gold in full, 2 calls a day on a free account): https://intel.threadlinqs.com/mcp

Canonical: https://intel.threadlinqs.com/threat/TL-2026-6885