CVE-2026-28252 - Trane Tracer SC/SC+/Concierge Broken Cryptographic Algorithm Authentication Bypass

highMONITORING

CVE-2026-28252 is a use of a broken or risky cryptographic algorithm (CWE-327) in Trane Tracer SC, Tracer SC+ and Tracer Concierge building-automation controllers. It lets an attacker bypass authentication and obtain root-level access to the device. CISA reports no known public exploitation at publication. First disclosed .

Key facts for Trane Tracer auth bypass

IdentifiersTL-2026-3567, CVE-2026-28252
Also known asICSA-26-071-01
SeverityHIGH
CVSS8.1 (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H)
First disclosed
Exploitation statusPublic proof-of-concept exploit
EPSSCVE-2026-28252: 0.2% (13.1th percentile)
Affected productsTrane Tracer SC; Trane Tracer SC+; Trane Tracer Concierge
Weaknesses (CWE)CWE-327
MITRE ATT&CK techniquesT1021.004 Remote Services, T1059 Command and Scripting Interpreter, T1059.004 Command and Scripting Interpreter, T1078 Valid Accounts, T1190 Exploit Public-Facing Application, T1499.004 Endpoint Denial of Service, T1552.001 Unsecured Credentials, T1590.004 Gather Victim Network Information
MotivationUNKNOWN
Target sectorscritical manufacturing, building automation, commercial facilities, data centers
Target regionsGlobal
Detection rules9 (1 shown free)
Sources8 cited sources

Detection coverage for Trane Tracer auth bypass

As of 2026-10-28, Threadlinqs Intelligence publishes 9 detection rule(s) for TL-2026-3567 across Splunk SPL, Microsoft KQL and Sigma, covering 17 indicator(s) of compromise. The whole corpus is readable without an account. Every threat comes with one complete detection in Splunk SPL, Microsoft KQL and Sigma, free for everyone; a free account adds daily TL Creds to unlock the rest. Paid plans add a larger daily allowance, correlation and the MCP server. Threadlinqs MCP server · View plans.

Free detection: CVE-2026-28252 Trane Tracer Web Management Access from Unauthorized Source

Detects allowed HTTP/HTTPS (TCP/80, TCP/443) sessions to Trane Tracer SC / SC+ / Concierge controllers from any source not on the approved engineering/BMS allow-list. CVE-2026-28252 (CWE-327) permits network authentication bypass to root-level access, so an unexpected source reaching the controller web interface is the earliest observable exploitation signal (T1190), indicates externally reachable management services (T1133), and a source touching several controllers is consistent with vulnerability scanning (T1595.002). Based on CISA ICSA-26-071-01 and secondary monitoring guidance; no public exploit or network IOC exists.

  • Languages: Splunk SPL, Microsoft KQL, Sigma
  • ATT&CK: T1190, T1133, T1595.002
  • Data sources: firewall:pan:traffic, CommonSecurityLog, network_traffic
  • Severity: high
  • Confidence: medium

Splunk SPL

index=firewall sourcetype="pan:traffic" (dest_port=80 OR dest_port=443) action=allowed
```comment: tracer_controllers.csv lists Trane Tracer SC/SC+/Concierge dest_ip (CIDR match type); tracer_authorized_sources.csv lists approved BMS/engineering src_ip```
| lookup tracer_controllers.csv dest_ip OUTPUT controller_model
| where isnotnull(controller_model)
| lookup tracer_authorized_sources.csv src_ip OUTPUT authorized
| where isnull(authorized)
| stats count AS sessions dc(dest_ip) AS controllers values(controller_model) AS models min(_time) AS first_seen max(_time) AS last_seen BY src_ip dest_port
| eval scan_like=if(controllers>=3,"yes","no"), rule="TL-2026-3567 CVE-2026-28252 Trane Tracer unauthorized web access T1190 T1133 T1595.002"

Microsoft KQL

let Controllers = _GetWatchlist('TraneTracerControllers') | project DestinationIP = tostring(SearchKey);
let AuthorizedSources = _GetWatchlist('TraneTracerAuthorizedSources') | project SourceIP = tostring(SearchKey);
CommonSecurityLog
| where TimeGenerated > ago(24h)
| where DestinationPort in (80, 443) and DeviceAction !in~ ("deny", "drop", "block")
| where DestinationIP in (Controllers)
| where SourceIP !in (AuthorizedSources)
| summarize Sessions = count(), ControllersTouched = dcount(DestinationIP), FirstSeen = min(TimeGenerated), LastSeen = max(TimeGenerated) by SourceIP, DestinationIP, DestinationPort
| extend ScanLike = ControllersTouched >= 3
| project FirstSeen, LastSeen, SourceIP, DestinationIP, DestinationPort, Sessions, ScanLike

Sigma

title: Trane Tracer Controller Web Access from Non-Management Source (CVE-2026-28252)
id: 6f1d2c3a-8b47-4e19-9a55-3c7e1b2d4a01
status: experimental
description: Detects allowed HTTP/HTTPS sessions to Trane Tracer SC/SC+/Concierge controller subnets from sources outside the approved management ranges. Indicator of exploitation attempts against the CVE-2026-28252 authentication bypass, externally reachable management interfaces, or vulnerability scanning of controllers.
references:
    - https://www.cisa.gov/news-events/ics-advisories/icsa-26-071-01
    - https://it.claroty.com/team82/disclosure-dashboard/cve-2026-28252
author: AII-Detector — ThreadLinqs Intelligence
date: 2026/10/14
tags:
    - attack.initial_access
    - attack.t1190
    - attack.persistence
    - attack.t1133
    - attack.reconnaissance
    - attack.t1595.002
    - cve.2026.28252
logsource:
    category: firewall
detection:
    selection:
        dst_port:
            - 80
            - 443
        dst_ip|cidr: 10.50.0.0/16
    filter_mgmt:
        src_ip|cidr:
            - 10.50.10.0/24
    filter_blocked:
        action:
            - deny
            - drop
            - blocked
    condition: selection and not 1 of filter_*
falsepositives:
    - Building engineers or integrators using unlisted workstations
    - Vulnerability scanners (e.g. Tenable OT plugin 505312) scanning controller subnets
level: high

Known false positives:

  • Authorized integrators or BMS engineers connecting from workstations not yet in the allow-list
  • Authenticated vulnerability scanners (e.g. Tenable OT plugin 505312) assessing controllers for CVE-2026-28252

Tuning notes: Populate tracer_controllers.csv (or the TraneTracerControllers watchlist) from the asset inventory and replace the example 10.50.0.0/16 and 10.50.10.0/24 ranges in the Sigma rule with real controller and management subnets. Add scanner IPs to the allow-list. scan_like=yes (3+ controllers from one source) raises priority. Adjust sourcetype/index for non-Palo Alto firewalls.

8 more detection rules (Splunk SPL, Microsoft KQL, Sigma) · unlock with TL Creds. Sign up free to unlock the detection rules or query them with the Threadlinqs MCP server (Purple)
  • High-Rate Web Requests to Tracer Controller (Authentication Bypass Probing) · unlock with TL Creds
  • Shell or Download Utility Spawned by Web Service on Tracer Controller (Command Execution After Root Access) · unlock with TL Creds
  • Tracer Controller Communication Gap or BACnet Flood (DoS Indicator) · unlock with TL Creds
  • External Source Reaching Tracer Controller Web Interface (Internet Exposure) · unlock with TL Creds
  • Unauthenticated Web Session Followed by Root Activity on Tracer Controller · unlock with TL Creds
  • Public-Source BACnet/IP Traffic to Building Controllers · unlock with TL Creds
  • Root Login on Trane Tracer Controller from Non-Management Source · unlock with TL Creds
  • BACnet/IP (UDP 47808) Traffic to Tracer Controllers from Unauthorized Subnets · unlock with TL Creds

Indicators of compromise for Trane Tracer auth bypass

As of 2026-10-28, Threadlinqs Intelligence tracks 17 indicators of compromise for TL-2026-3567.

17 indicators of compromise · unlock with TL Creds. Compare plans

How Trane Tracer auth bypass works

CVE-2026-28252 affects Trane Tracer SC, Tracer SC+ and Tracer Concierge building-automation controllers and is tracked by CISA in ICS Advisory ICSA-26-071-01 (released 2026-03-12). The flaw is classified as CWE-327 (Use of a Broken or Risky Cryptographic Algorithm). Per the CVE record, an attacker can bypass authentication and gain root-level access to the device. Per Claroty Team82, consequences include sensitive information disclosure, arbitrary command execution or denial of service.

Scoring differs by source. CISA and Claroty list CVSS v3 8.1 HIGH (AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H), the high attack complexity reflecting the cryptographic weakness that must be defeated. NVD and Tenable list CVSS v3.1 9.8 CRITICAL (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H) and CVSS v4.0 9.2 (AV:N/AC:H/AT:P). This record uses the CISA/Claroty 8.1 value. The public sources reviewed do not publish the specific algorithm weakness or an exploit procedure, and no PoC is referenced.

Affected versions per CISA: Tracer SC before v4.4_SP7, and Tracer SC+ and Tracer Concierge before v6.3.2310. The advisory names Tracer SC+ v6.30.2313 as the fixed release that addresses CVE-2026-28252, CVE-2026-28253 and CVE-2026-28254. The same advisory covers CVE-2026-28253 (memory allocation overflow, DoS, CVSS 7.5), CVE-2026-28254 (missing authorization, 5.8), CVE-2026-28255 (hard-coded credentials, 6.8) and CVE-2026-28256 (hard-coded security constants, 5.8). The vulnerability was reported by Noam Moshe of Claroty Team82. CISA lists the Critical Manufacturing sector. CISA states that no known public exploitation specifically targeting these vulnerabilities has been reported to it.

CISA mitigations: network isolation of controllers, VPN for remote access, firewall protection and Trane cloud security controls. Secondary reporting suggests monitoring BACnet (UDP 47808) and HTTP/HTTPS (80/443) access to controllers from unauthorized subnets, and watching for communication gaps or device unresponsiveness as DoS indicators. That guidance comes from a secondary blog, not the advisory. The sources do not provide network IOCs, malware, or actor attribution, so no BeaconBeagle correlation applies.

MITRE ATT&CK techniques by tactic:

Lateral Movement

T1021.004 Remote Services

Execution

T1059 Command and Scripting Interpreter; T1059.004 Command and Scripting Interpreter

Privilege Escalation

T1078 Valid Accounts

Defense Evasion

T1078 Valid Accounts

Initial Access

T1190 Exploit Public-Facing Application

Impact

T1499.004 Endpoint Denial of Service

Credential Access

T1552.001 Unsecured Credentials

Reconnaissance

T1590.004 Gather Victim Network Information

Remediation for Trane Tracer auth bypass

Patches

  • Tracer SC+ v6.30.2313 (fixes CVE-2026-28252, CVE-2026-28253, CVE-2026-28254)
  • Tracer SC v4.4_SP7 or later per CISA affected-version boundary

Immediate actions

  • Upgrade Tracer SC+ and Tracer Concierge to v6.30.2313 or later; upgrade Tracer SC to v4.4_SP7 or later
  • Remove controllers from direct internet exposure and isolate them behind firewalls
  • Verify by port scan that controllers are not reachable from the internet or the corporate network

Workarounds

  • Enable Trane cloud security controls per CISA advisory ICSA-26-071-01
  • Restrict network access to controller management interfaces

Longer-term hardening

  • Segment building-automation/OT networks onto dedicated VLANs
  • Provide remote access only through patched VPNs
  • Monitor BACnet and web-management traffic to controllers from unauthorized subnets

Affected and fixed versions

  • Trane — Tracer SC
    Vulnerable versions: < v4.4_SP7
    Fixed in: v4.4_SP7
  • Trane — Tracer SC+
    Vulnerable versions: < v6.3.2310
    Fixed in: v6.30.2313
  • Trane — Tracer Concierge
    Vulnerable versions: < v6.3.2310
    Fixed in: v6.30.2313

Timeline of Trane Tracer auth bypass

Last updated · revalidated 1× · latest source

  • CVE-2026-28252 reserved in the CVE program.
  • locked-ioc-17 releases Tracer SC+ v6.3 (per Claroty), the first fixed release line; v6.30.2313 is the version locked-ioc-17 later recommends.
  • CISA states no known public exploitation targeting these vulnerabilities has been reported to it
  • Vulnerability credited to locked-ioc-15 of locked-ioc-14 in the CISA advisory; Team82 lists it on its disclosure dashboard
  • Fixed firmware made available; locked-ioc-10 addresses CVE-2026-28252, CVE-2026-28253 and CVE-2026-28254 (patch date per Tenable/CISA)
  • CVE-2026-28252 is published to NVD; NVD lists CVSS v3.1 9.8 and CVSS v4.0 9.2, CWE-327
  • CISA publishes ICS Advisory ICSA-26-071-01 covering CVE-2026-28252 through CVE-2026-28256 in locked-ioc-13, SC+ and Concierge; CVE-2026-28252 is rated CVSS v3 8.1 HIGH
  • Tenable publishes OT Security plugin 505312 to detect vulnerable locked-ioc-17 Tracer devices for CVE-2026-28252
  • locked-ioc-14 publishes 'Turning Up the Heat: Hacking locked-ioc-17 HVAC Controllers' detailing the PAM challenge-response flaw (deterministic algorithm, no secret), the chained CVEs and the exploitation path.

Update history

Sources cited for Trane Tracer auth bypass

Other reports on CVE-2026-28252

Previous and next in ics scada

Drafted by the Threadlinqs research pipeline from 8 sources; published ; last updated .

Threadlinqs Intelligence — Real-Time Threat Detection Platform

[ 0 threats ] [ 0 det ] [ CRIT: 0 ] [ HIGH: 0 ]
// threat_feed
$ sort --newest
Showing all threats

Live intelligence console

Threat level

Latest Threats