Threat reportICS/SCADATL-2026-3568

CVE-2025-13902 - Schneider Electric Modicon M241/M251/M262 (and M258/LMC058) Controllers Stored Cross-Site Scripting (CWE-79)

mediumMONITORING

CVE-2025-13902 (TL-2026-3568), also tracked as SEVD-2026-069-01, is a medium-severity ICS/SCADA threat scored CVSS 5.4, first published 2026-10-15. It has no confirmed attribution, affects Schneider Electric Modicon Controllers M241/M251, references 1 CVE (CVE-2025-13902), maps to 5 MITRE ATT&CK techniques (T1059.007, T1078, T1185), and is covered by 9 detection rules and 12 indicators of compromise.

CVSS
5.4/10Medium
CVEs
1Referenced vulnerabilities
Techniques
5MITRE ATT&CK
Actors
0Not attributed
Detection rules
9SPL · KQL · Sigma
IOCs
12Indicators of compromise

Key facts for TL-2026-3568

Threat ID
TL-2026-3568
Also known as
SEVD-2026-069-01, SEVD-2026-069-02
Severity
MEDIUM
CVSS
5.4 (CVSS:3.0/AV:N/AC:L/PR:L/UI:R/S:C/C:L/I:L/A:N)
Status
MONITORING
Category
ICS_SCADA
First published
Last reviewed
Attribution confidence
LOW
Motivation
UNKNOWN
Target sectors
manufacturing, energy, critical-infrastructure, industrial-automation
Target regions
Global
Detection rules
9
Indicators of compromise
12

How CVE-2025-13902 works

CVE-2025-13902 is a CWE-79 cross-site scripting flaw in the embedded web server of Schneider Electric Modicon M241/M251/M262 controllers (the CVE record also lists M258 and LMC058). An authenticated attacker can inject a payload that runs arbitrary JavaScript in a victim's browser when the victim hovers over the crafted element. No exploitation in the wild, public PoC or KEV listing is documented.

CVE-2025-13902 was reserved on 2025-12-02 and published on 2026-03-10. It is disclosed through Schneider Electric security notice SEVD-2026-069 and listed on the Claroty Team82 disclosure dashboard. The CVE record text states that authenticated attackers can have a victim's browser run arbitrary JavaScript when the victim hovers over a maliciously crafted element on a web server containing the injected payload. The weakness class is CWE-79 (improper neutralization of input during web page generation).

Affected scope according to the CVE record: Modicon Controllers M241/M251 firmware prior to 5.4.13.12, and Modicon M258/LMC058 (all versions). The Claroty dashboard lists M241/M251/M262. Shodan CVEDB also maps the CVE to CPEs for M241/M251 firmware 4.0.3.20 and 5.1.9.1. Source discrepancy: the Claroty page and the hunt skeleton name M262, while the CVE record and CPE data name M258/LMC058 and do not name M262. The skeleton references advisory SEVD-2026-069-01 while the CVE record references SEVD-2026-069-02. The vendor PDFs could not be machine-parsed in this run, so fixed versions for M262 and any vendor workarounds are not confirmed here.

Severity: Tenable reports CVSS v3.0 5.4 (CVSS:3.0/AV:N/AC:L/PR:L/UI:R/S:C/C:L/I:L/A:N), CVSS v2 5.5 and CVSS v4.0 5.1 (CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:P/VC:N/VI:N/VA:N/SC:L/SI:L/SA:N). The attack requires a low-privileged authenticated account plus user interaction (a hover) and changes scope to the victim's browser context. Shodan CVEDB reports KEV: No and EPSS 0.00234. No public PoC, exploitation reporting, named threat actor, network IOC or malware is associated with this CVE in any source reviewed.

Defensive relevance: the realistic abuse path is an authenticated user (or stolen/default credentials) planting a script payload in a web-served element of a controller's HTTP interface, which then executes in the session of an engineer or operator who views it. Impact is limited (low confidentiality and integrity per the CVSS vectors, no availability impact), but it can serve as a foothold against the engineering browser session in an OT environment. Defenders should inventory exposed Modicon web servers, restrict access, and apply the vendor firmware update where available.

MITRE ATT&CK techniques used in TL-2026-3568

Execution

T1059.007 JavaScript; T1204 User Execution

Initial Access

T1078 Valid Accounts; T1190 Exploit Public-Facing Application

Collection

T1185 Browser Session Hijacking

Affected products and versions in CVE-2025-13902

  • Schneider Electric — Modicon Controllers M241/M251
    Vulnerable versions: firmware prior to 5.4.13.12
    Fixed in: 5.4.13.12
  • Schneider Electric — Modicon Controllers M258/LMC058
    Vulnerable versions: all versions
  • Schneider Electric — Modicon Controller M262
    Vulnerable versions: listed by Claroty Team82; versions not stated in sources reviewed

Remediation for CVE-2025-13902

Patches

  • Modicon M241/M251: update firmware to 5.4.13.12 or later (CVE record lists versions prior to 5.4.13.12 as affected)

Immediate actions

  • Identify Modicon M241/M251/M262/M258/LMC058 controllers with the embedded web server reachable and restrict access to trusted engineering networks
  • Review and minimise accounts able to authenticate to the controller web server and rotate their credentials
  • Read Schneider Electric notice SEVD-2026-069 (-01 and -02) for product-specific fixes and mitigations

Workarounds

  • M258/LMC058: the CVE record lists all versions as affected; consult the vendor advisory for mitigations as no fixed version is stated in the sources reviewed

Longer-term hardening

  • Segment OT networks and keep controller web interfaces off the internet
  • Use hardened engineering workstations and browsers when accessing controller web interfaces

CVEs associated with CVE-2025-13902

CVE-2025-13902

Weaknesses (CWE) in CVE-2025-13902

CWE-79

Timeline of CVE-2025-13902

  • CVE-2025-13902 reserved in the CVE Program.
  • Patch publication date recorded as 2026-03-10; M241/M251 firmware 5.4.13.12 is the first non-vulnerable version per the CVE record.
  • CVE record published; Schneider Electric advisory SEVD-2026-069 released and the vulnerability publication date recorded by Tenable.
  • CVEfeed records the CVE entry as last modified.
  • Tenable OT plugin 505937 published for Schneider Electric Modicon Controllers.
  • Tenable OT plugin 505937 updated.

Sources cited for CVE-2025-13902

Detection coverage for TL-2026-3568

As of 2026-10-15, Threadlinqs Intelligence publishes 9 detection rule(s) for TL-2026-3568 across Splunk SPL, Microsoft KQL and Sigma, covering 12 indicator(s) of compromise. The whole corpus is readable without an account; a free account unlocks full detection query text in Splunk SPL, Microsoft KQL and Sigma; paid tiers add raw indicator values, correlation and the MCP server. Threadlinqs MCP server · View plans.

9 detection rules (Splunk SPL, Microsoft KQL, Sigma) · Blue and above. Compare plans
12 indicators of compromise · Red and above. Compare plans