Skip to navigation

Threat reportVulnerabilityTL-2026-4460

Multiple vulnerabilities in boneIO Black and black_debian_images, including unauthenticated Node-RED RCE (CVE-2026-77052 through CVE-2026-77062)

highPATCHED

CERT Polska disclosed 11 vulnerabilities on 2026-10-26 in the boneIO Black DIN-rail home-automation controller (boneIO app) and its black_debian_images firmware. The flaws include an unauthenticated Node-RED instance enabling remote code execution, authentication disabled by default, cleartext credentials, shared default MQTT credentials and passwordless sudo/docker privileges.

Key facts

IdentifiersTL-2026-4460, CVE-2026-77052, CVE-2026-77053, CVE-2026-77054, CVE-2026-77055, CVE-2026-77056, CVE-2026-77057, CVE-2026-77058, CVE-2026-77059, CVE-2026-77060, CVE-2026-77061, CVE-2026-77062
Also known asboneIO Black vulnerabilities, black_debian_images vulnerabilities
SeverityHIGH
CVSS8.7 (CVSS:4.0/AV:A/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:L/SI:L/SA:L)
First disclosed
EPSSCVE-2026-77062: 0.5% (44.5th percentile); CVE-2026-77056: 0.3% (29.2th percentile); CVE-2026-77052: 0.3% (26.3th percentile)
Affected productsboneIO boneIO (app_black, boneIO Black web UI/API); boneIO black_debian_images
Weaknesses (CWE)CWE-306, CWE-312, CWE-266, CWE-1392, CWE-307, CWE-352, CWE-367, CWE-732, CWE-1021
ToolsCaddy, Mosquitto, Node-RED
MITRE ATT&CK techniquesT1059.004 Command and Scripting Interpreter: Unix Shell, T1078.001 Valid Accounts: Default Accounts, T1082 System Information Discovery, T1110.001 Brute Force: Password Guessing, T1110.002 Brute Force: Password Cracking, T1190 Exploit Public-Facing Application, T1529 System Shutdown/Reboot, T1548.003 Abuse Elevation Control Mechanism: Sudo and Sudo Caching, T1552.001 Unsecured Credentials: Credentials In Files, T1611 Escape to Host
MotivationUNKNOWN
Target sectorssmart-home, building-automation, residential
Detection rules9 (1 shown free)
Sources9 cited sources

Detection coverage

As of 2026-10-26, Threadlinqs Intelligence publishes 9 detection rule(s) for TL-2026-4460 across Splunk SPL, Microsoft KQL and Sigma, covering 14 indicator(s) of compromise. The whole corpus is readable without an account. Every threat comes with one complete detection in Splunk SPL, Microsoft KQL and Sigma, free for everyone; a free account adds daily TL Creds to unlock the rest. Paid plans add a larger daily allowance, correlation and the MCP server. Threadlinqs MCP server · View plans.

Free detection: boneIO Black Unauthenticated Node-RED Admin API Flow Deployment (CVE-2026-77052) — Exploitation

Detects write requests to the Node-RED Admin API exposed at /nodered/ behind Caddy on boneIO Black controllers (CVE-2026-77052, CWE-306). Deploying a flow through POST /nodered/flows lets an adjacent-network attacker run arbitrary system commands via exec nodes as the boneio account, which CVE-2026-77055 then turns into root. No authentication is required on versions 1.3.0 to before 1.6.0, so any POST/PUT/DELETE to the flow, node, settings or token endpoints from a host other than the administrator workstation is suspicious.

  • Languages: Splunk SPL, Microsoft KQL, Sigma
  • ATT&CK: T1190, T1059.004
  • Data sources: caddy_access_logs, web_proxy_logs
  • Severity: critical
  • Confidence: high

Splunk SPL

index=web sourcetype="caddy:json" "/nodered/"
| eval uri='request.uri', method='request.method', src_ip='request.remote_ip', req_host='request.host'
| where match(uri, "(?i)^/nodered/(flows?|nodes|settings|auth/token)") AND method IN ("POST","PUT","DELETE")
| stats count AS requests earliest(_time) AS first_seen latest(_time) AS last_seen values(uri) AS uris values(status) AS http_status BY src_ip, req_host
| convert ctime(first_seen) ctime(last_seen)
| sort - requests

Microsoft KQL

CommonSecurityLog
| where TimeGenerated > ago(24h)
| where RequestURL has "/nodered/"
| where RequestMethod in~ ("POST", "PUT", "DELETE")
| where RequestURL matches regex @"(?i)/nodered/(flows?|nodes|settings|auth/token)"
| summarize Requests = count(), FirstSeen = min(TimeGenerated), LastSeen = max(TimeGenerated), Urls = make_set(RequestURL, 20) by SourceIP, DestinationIP, DestinationPort
| project FirstSeen, LastSeen, SourceIP, DestinationIP, DestinationPort, Requests, Urls
| order by Requests desc

Sigma

title: boneIO Black Node-RED Admin API Flow Deployment Without Authentication
id: a1b2c3d4-4460-4a01-8b01-446000000001
status: experimental
description: Detects POST/PUT/DELETE requests to the Node-RED Admin API under /nodered/ on boneIO Black controllers (CVE-2026-77052), which allow unauthenticated flow deployment and OS command execution.
references:
  - https://cert.pl/en/posts/2026/10/CVE-2026-77052/
  - https://nvd.nist.gov/vuln/detail/CVE-2026-77052
author: Threadlinqs Team
date: 2026/10/26
tags:
  - attack.initial-access
  - attack.t1190
  - attack.execution
  - attack.t1059.004
  - cve.2026.77052
logsource:
  category: webserver
detection:
  selection_uri:
    c-uri|contains:
      - '/nodered/flow'
      - '/nodered/nodes'
      - '/nodered/settings'
      - '/nodered/auth/token'
  selection_method:
    cs-method:
      - 'POST'
      - 'PUT'
      - 'DELETE'
  filter_local:
    c-ip:
      - '127.0.0.1'
      - '::1'
  condition: selection_uri and selection_method and not filter_local
falsepositives:
  - Administrator deploying Node-RED flows from a management workstation
  - Home Assistant or provisioning tooling that legitimately pushes flows
level: high

Known false positives:

  • Administrator deploying Node-RED flows from a management workstation
  • Provisioning or Home Assistant tooling that legitimately pushes flows to Node-RED

Tuning notes: Allowlist the management workstation IPs in the where clause. Change index/sourcetype to match your Caddy JSON log onboarding. Version 1.6.0 requires authentication, so after patching, a 401 status in http_status can be excluded to cut noise.

8 more detection rules (Splunk SPL, Microsoft KQL, Sigma) · unlock with TL Creds. Sign up free to unlock the detection rules or query them with the Threadlinqs MCP server (Purple)
  • [indicator] Black Unauthenticated [indicator] Retrieval Exposing Cleartext Passwords (CVE-2026-77054) — Exploitation · unlock with TL Creds
  • [indicator] Sudoers Drop-in Creation or Symlink Race (CVE-2026-77059) — Post-Exploitation · unlock with TL Creds
  • [indicator] Controller SSH and Web Login Brute Force Without Rate Limiting (CVE-2026-77057) — Credential Access · unlock with TL Creds
  • [indicator] Black Cross-Site Request Forgery Device Control / Reboot (CVE-2026-77058) — Exploitation · unlock with TL Creds
  • [indicator] Local Read of World-Readable Mosquitto Password File (CVE-2026-77060) — Post-Exploitation · unlock with TL Creds
  • [indicator] Unauthenticated API Reconnaissance of Logs, Version and Documentation (CVE-2026-77061) — Discovery · unlock with TL Creds
  • [indicator] Service Account Passwordless Sudo to Root Shell or Privileged Docker (CVE-2026-77055) — Post-Exploitation · unlock with TL Creds
  • [indicator] Mosquitto Broker Connection From Non-Local Host With Shared Default Credentials (CVE-2026-77056) — C2 / Lateral Movement · unlock with TL Creds

Indicators of compromise

As of 2026-10-26, Threadlinqs Intelligence tracks 14 indicators of compromise for TL-2026-4460.

14 indicators of compromise · unlock with TL Creds. Compare plans

Technical analysis

All are fixed in version 1.6.0.

CERT Polska (CVD coordinator) published an advisory on 2026-10-26, credited to Mateusz Włodarczak (s3ga), covering eleven CVEs in boneIO Black, a DIN-rail home-automation controller running Debian with Caddy, Mosquitto (MQTT), Node-RED and Home Assistant integration. The web UI is served at https://<controller IP>:8443. NVD records were published the same day with CVSS v4.0 scores.

Remote / adjacent-network attack surface: CVE-2026-77052 (CWE-306, CVSS 4.0 8.7 HIGH) exposes an unauthenticated Node-RED instance at /nodered/ behind a Caddy reverse proxy; the Node-RED Admin API allows deploying flows that run arbitrary system commands, giving unauthenticated attackers on the local network remote code execution (affected 1.3.0 up to 1.6.0). CVE-2026-77053 (CWE-306, 8.7 HIGH) ships with authentication disabled by default and an API listening on all interfaces, allowing full device control including operating connected physical circuits (relays, blinds, gates). CVE-2026-77061 (CWE-306, 5.3 MEDIUM) leaves several API endpoints unauthenticated, leaking system logs, firmware version, serial number, MQTT username, configuration file listings and API documentation. CVE-2026-77054 (CWE-312, 6.9 MEDIUM) stores passwords in cleartext and returns the full configuration, including sub-service passwords, from GET /api/config; combined with CVE-2026-77053 an unauthenticated adjacent attacker can harvest all passwords. CVE-2026-77056 (CWE-1392, 7.1 HIGH) ships the Mosquitto MQTT broker with the same publicly documented default credentials on all devices, giving full read/write on the broker, control of relays, blinds and gates, and the ability to inject fake entities into a linked Home Assistant. CVE-2026-77057 (CWE-307, 2.3 LOW) has no rate limiting on web login or SSH and no password complexity enforcement. CVE-2026-77058 (CWE-352, 5.1 MEDIUM) lacks CSRF tokens and Origin/Referer validation, allowing a malicious page visited by an internal user to reboot the controller, switch relays, operate gates and blinds, or terminate the device; the default-disabled authentication amplifies the risk. CVE-2026-77062 (CWE-1021) lacks clickjacking protections (frame/iframe restrictions); an NVD score could not be retrieved at research time.

Local privilege-escalation surface: CVE-2026-77055 (CWE-266, 9.3 CRITICAL, local) gives the boneio service account full passwordless sudo and docker group membership, so a compromised boneio account (for example via the Node-RED RCE) becomes root. CVE-2026-77059 (CWE-367, 8.8 HIGH, local) is a TOCTOU race in create_timedatectl_sudoers_file() in boneio/webui/routes/timezone_sudoers.py that allows sudoers rule injection via content substitution or symlink attacks on a predictable filename, leading to root. CVE-2026-77060 (CWE-732, 6.8 MEDIUM, local) leaves /etc/mosquitto/passwd world-readable so any local user can read MQTT password hashes and mount offline dictionary attacks.

Chaining the adjacent-network flaws (77053 / 77052 / 77054) with the local ones (77055 / 77059) yields unauthenticated network-adjacent root on the controller, a pivot point into the building network and Home Assistant. Remediation in 1.6.0: enforced admin account creation and role-based access control, authentication on all routes with API docs disabled, salted scrypt password hashes with secrets no longer returned by the API, per-device generated MQTT passwords at first boot, removal of the sudoers rules and docker group membership with privileged operations via restricted helpers verifying Ed25519 signatures, web-login rate limiting per source and account, 8-character minimum password and SSH limited to three attempts per connection. Devices below 1.2.0 require re-flashing rather than in-place upgrade.

Source caveats: the CERT Polska page lists 1.6.0 both as fixed and within the affected range; NVD states affected versions are prior to 1.6.0, which this record follows. NVD labels CWE-307 for CVE-2026-77057 with a different title (UI layer restriction); CERT Polska's CWE-307 (excessive authentication attempts) matches the described behavior and is used. The sources do not state a public PoC, in-the-wild exploitation, CISA KEV listing, threat actor or network IOCs. CVE-2026-77052 / CVE-2026-77053 are the headline scores; the record's CVSS is the 4.0 score and vector from the NVD entry for CVE-2026-77053.

MITRE ATT&CK techniques by tactic:

Execution

T1059.004 Command and Scripting Interpreter: Unix Shell

Initial Access

T1078.001 Valid Accounts: Default Accounts; T1190 Exploit Public-Facing Application

Discovery

T1082 System Information Discovery

Credential Access

T1110.001 Brute Force: Password Guessing; T1110.002 Brute Force: Password Cracking; T1552.001 Unsecured Credentials: Credentials In Files

Impact

T1529 System Shutdown/Reboot

Privilege Escalation

T1548.003 Abuse Elevation Control Mechanism: Sudo and Sudo Caching; T1611 Escape to Host

Remediation

Patches

  • boneIO 1.6.0 (CERT Polska advisory, NVD CVE-2026-77052 to CVE-2026-77062)

Immediate actions

  • Upgrade boneIO Black / black_debian_images to version 1.6.0 or later (devices below 1.2.0 must be re-flashed)
  • Complete first-run administrator account setup so authentication is enforced on all API routes
  • Rotate all MQTT, web panel and SSH passwords and any credentials previously returned by /api/config
  • Restrict access to the controller (https port 8443, /nodered/, MQTT 1883) to a dedicated management VLAN

Workarounds

  • Do not expose the controller to untrusted networks while authentication is disabled
  • Block /nodered/ at a reverse proxy or firewall until upgraded
  • Do not browse untrusted sites from hosts on the same network as an unpatched controller (CSRF/clickjacking)

Longer-term hardening

  • Isolate building-automation controllers from user and internet-facing networks
  • Monitor MQTT broker and Home Assistant for unexpected publishers or injected entities
  • Alert on new sudoers.d files and docker group changes on controllers

Affected and fixed versions

  • boneIO — boneIO (app_black, boneIO Black web UI/API)
    Vulnerable versions: 1.0.0 to before 1.6.0 (CVE-2026-77053); 1.2.0 to before 1.6.0 (CVE-2026-77054, 77057, 77058, 77061, 77062); 1.3.0 to before 1.6.0 (CVE-2026-77052, 77059)
    Fixed in: 1.6.0
  • boneIO — black_debian_images
    Vulnerable versions: 1.2.0 to before 1.6.0 (CVE-2026-77055, 77056, 77060)
    Fixed in: 1.6.0

Timeline

  • Advisory and NVD records state no public PoC and no in-the-wild exploitation; no KEV listing identified
  • Local privilege-escalation flaws CVE-2026-77055 (9.3 CRITICAL) and CVE-2026-77059 (8.8 HIGH) rated; chaining with the network RCE gives root on the controller
  • CVE-2026-77052 (unauthenticated Node-RED /nodered/ RCE) and CVE-2026-77053 (authentication disabled by default) rated CVSS 4.0 8.7 HIGH, adjacent-network attack vector
  • boneIO 1.6.0 identified as the fixed version: enforced admin setup and RBAC, scrypt password hashing, per-device MQTT passwords, removal of passwordless sudo/docker membership, login rate limiting
  • NVD published records for the CVEs with CVSS v4.0 scores ranging from 2.3 (CVE-2026-77057) to 9.3 (CVE-2026-77055)
  • CERT Polska published a coordinated-disclosure advisory covering 11 vulnerabilities (CVE-2026-77052 to CVE-2026-77062) in boneIO and black_debian_images, credited to Mateusz Włodarczak (s3ga)

Sources cited

Previous and next in vulnerability

Drafted by the Threadlinqs research pipeline from 9 sources; published ; last updated —.

Threadlinqs Intelligence — Real-Time Threat Detection Platform

// threat_feed
$ sort --newest
Showing all threats

Live intelligence console

Threat level

Latest Threats