Skip to navigation

Threat reportICS/SCADATL-2026-6515

RDM Refrigeration Controller Vulnerabilities - UK Supermarket Cold Chain Exposure (NCSC Urgent Alert)

highTRACKING

Neil McCourt (Omega Solutions) found a significant vulnerability in RDM refrigeration controllers widely used in UK retail; Pen Test Partners (Andrew Tierney) validated it and found additional vulnerabilities. NCSC issued an urgent alert to UK supermarkets and RDM released new firmware (advisory RDM-SA-2026-001), but smaller cold chain operators with internet-exposed controllers may still be at risk.

Key facts

IdentifiersTL-2026-6515
Also known asRDM-SA-2026-001
SeverityHIGH
First disclosed
Affected productsRDM (Resource Data Management) Refrigeration controllers (models not disclosed)
ToolsShodan
MITRE ATT&CK techniquesT1190 Exploit Public-Facing Application, T1596.005 Scan Databases
MotivationUNKNOWN
Target sectorsretail, food-and-agriculture, cold-storage, commercial-facilities, food-manufacturing
Target regionsunited kingdom, Europe
Detection rules9 (1 shown free)
Sources9 cited sources

Detection coverage

As of 2026-11-20, Threadlinqs Intelligence publishes 9 detection rule(s) for TL-2026-6515 across Splunk SPL, Microsoft KQL and Sigma, covering 11 indicator(s) of compromise. The whole corpus is readable without an account. Every threat comes with one complete detection in Splunk SPL, Microsoft KQL and Sigma, free for everyone; a free account adds daily TL Creds to unlock the rest. Paid plans add a larger daily allowance, correlation and the MCP server. Threadlinqs MCP server · View plans.

Free detection: RDM Refrigeration Controller Management Interface Reached from Non-Allowlisted Internet Source

Detects allowed inbound HTTP/HTTPS sessions from public IP space to known refrigeration controller assets (RDM / Danfoss class, e.g. controllers on cellular modems with public addressing) from sources not on the remote-access allowlist. This is the exposure-to-exploitation path for TL-2026-6515 (T1190): PTP found thousands of Shodan-discoverable controllers and the RDM flaw is only reachable if the management interface is exposed. No RDM exploit signature is public, so this detection is behaviour-first.

  • Languages: Splunk SPL, Microsoft KQL, Sigma
  • ATT&CK: T1190, T1133
  • Data sources: palo_alto_networks_traffic, firewall
  • Severity: high
  • Confidence: medium

Splunk SPL

index=network sourcetype="pan:traffic" earliest=-24h action=allowed dest_port IN (80,443,8080,8443) NOT (src_ip=10.0.0.0/8 OR src_ip=172.16.0.0/12 OR src_ip=192.168.0.0/16 OR src_ip=127.0.0.0/8) | lookup refrigeration_controller_assets.csv dest_ip OUTPUT controller_vendor site | where isnotnull(controller_vendor) | search NOT [| inputlookup remote_access_allowlist.csv | fields src_ip] | stats count AS sessions dc(dest_ip) AS controllers_reached sum(bytes_out) AS bytes_out values(dest_port) AS ports min(_time) AS first_seen max(_time) AS last_seen BY src_ip controller_vendor site | convert ctime(first_seen) ctime(last_seen) | eval detection_id="TL-2026-6515-SPL-001", threat="RDM refrigeration controller exposure T1190"

Microsoft KQL

let controllers = _GetWatchlist('RefrigerationControllers') | project DestinationIP = tostring(SearchKey);
let allowlist = _GetWatchlist('RemoteAccessAllowlist') | project SourceIP = tostring(SearchKey);
CommonSecurityLog
| where TimeGenerated > ago(24h)
| where DeviceAction in~ ("allow", "allowed", "accept", "permit")
| where DestinationPort in (80, 443, 8080, 8443)
| where not(ipv4_is_private(SourceIP))
| join kind=inner controllers on DestinationIP
| join kind=leftanti allowlist on SourceIP
| summarize Sessions = count(), ControllersReached = dcount(DestinationIP), Ports = make_set(DestinationPort), FirstSeen = min(TimeGenerated), LastSeen = max(TimeGenerated) by SourceIP
| project SourceIP, Sessions, ControllersReached, Ports, FirstSeen, LastSeen

Sigma

title: Internet Source Reaching Refrigeration Controller Web Management Interface
id: 6f1c2a5e-3b7d-4e18-9a52-7d0c4b1e6a01
status: experimental
description: Allowed inbound HTTP/HTTPS from public IPs into a firewall zone holding refrigeration controllers (TL-2026-6515, RDM-SA-2026-001 context). Requires dst_zone field mapping to your refrigeration/OT zone naming.
references:
    - https://www.pentestpartners.com/security-blog/the-fridge-hack-uk-supermarkets-narrowly-avoided/
    - https://www.cisa.gov/news-events/ics-advisories/icsa-25-140-03
author: Threadlinqs Team
date: 2026/11/20
tags:
    - attack.initial_access
    - attack.t1190
    - attack.t1133
logsource:
    category: firewall
detection:
    selection:
        action:
            - 'allow'
            - 'allowed'
            - 'accept'
        dst_port:
            - 80
            - 443
            - 8080
            - 8443
        dst_zone|contains:
            - 'refrig'
            - 'coldchain'
            - 'cold-chain'
    filter_private:
        src_ip|cidr:
            - '10.0.0.0/8'
            - '172.16.0.0/12'
            - '192.168.0.0/16'
            - '127.0.0.0/8'
    condition: selection and not filter_private
falsepositives:
    - Approved refrigeration contractor connecting from a fixed IP not yet on the allowlist
    - Vulnerability scanners run by the organisation
level: medium

Known false positives:

  • Approved refrigeration contractor connecting from an IP not yet on the allowlist
  • Authorised external vulnerability scans

Tuning notes: Populate refrigeration_controller_assets.csv (dest_ip, controller_vendor, site) and remote_access_allowlist.csv; include contractor and modem-APN ranges. Map dst_zone to your zone names for the Sigma flavour. Swap pan:traffic for your firewall sourcetype if needed.

8 more detection rules (Splunk SPL, Microsoft KQL, Sigma) · unlock with TL Creds. Sign up free to unlock the detection rules or query them with the Threadlinqs MCP server (Purple and Gold in full, 2 calls a day on a free account)
  • Public Internet Source Reaching Industrial/Building-Automation Protocol Ports (Modbus, BACnet, OPC UA, EtherNet/IP) · unlock with TL Creds
  • Defrost Heater and Alarm Parameter Manipulation from One Source (Cold-Chain Sabotage Pattern) · unlock with TL Creds
  • Refrigeration Controller or Cellular Modem Initiating Outbound Internet Connections to Non-Allowlisted Destinations · unlock with TL Creds
  • Internet-Sourced Request to Controller [indicator] Endpoint (Danfoss-Precedent Login Surface) · unlock with TL Creds
  • Internet-Sourced Defrost, Alarm or Setpoint Change Request on Refrigeration Controller · unlock with TL Creds
  • Internet Source Reaching Cellular Modem Management Ports (Telnet, SSH, SNMP, TR-069) · unlock with TL Creds
  • Bulk Configuration Writes Across Multiple Refrigeration Controllers from One Source (RDM/Danfoss Impact Pattern) · unlock with TL Creds
  • Single Internet Source Sweeping Five or More Refrigeration Controllers (Shodan-Style Enumeration and Fleet Targeting) · unlock with TL Creds

Indicators of compromise

As of 2026-11-20, Threadlinqs Intelligence tracks 11 indicators of compromise for TL-2026-6515.

11 indicators of compromise · unlock with TL Creds. Compare plans

Technical analysis

Pen Test Partners (PTP) reported on 2026-11-20 that a significant vulnerability in RDM (Resource Data Management) refrigeration controllers was discovered by Neil McCourt of Omega Solutions. Andrew Tierney of PTP validated the issue and found several further vulnerabilities, which were reported to RDM. The flaw is described as related to, but not identical with, the Danfoss controller issue behind the October 2026 French supermarket attacks. No CVE IDs, CVSS scores, RDM model numbers, firmware version numbers or vulnerability classes have been published, and PTP explicitly withholds exploit details and its discovery method. RDM controllers are the popular brand in UK retail, and PTP says RDM design decisions make them harder to find than the Danfoss devices were.

The common exposure mechanism is cellular modems placing controllers directly on the public internet, often installed by third-party refrigeration contractors for remote servicing. PTP states thousands of exposed controllers were identified using Shodan and open-source location data, with significant operators being mainly supermarkets, food manufacturers and large cold storage operators. Some supermarkets already had controllers on private networks or behind VPNs, which reduced exposure. A coordinated effort was made to locate exposed units and take them offline.

Omega Solutions took a detailed write-up to the UK NCSC, which issued an urgent alert to UK supermarkets through its channels (the article gives no date). PTP also notes involvement of the British Retail Consortium, DEFRA and the Food Standards Agency, and that it spoke with RDM's CEO and CTO, who were working on firmware around the clock. RDM sent customers advisory RDM-SA-2026-001 on 2 November 2026 (revised 3 November) and released new firmware said to address this and several other issues. PTP criticised the advisory for not describing attacker capability, not providing independent firmware validation, not crediting the reporter, and not confirming that deeper supply-chain users were notified. PTP describes the issue as largely mitigated but notes smaller cold chain operators may still be exposed; press reporting surfaced via search says NCSC confirmed vulnerable refrigeration technology had been exploited in a small number of UK incidents, though it is not established that those involved RDM devices.

Precedent: on the night of 11 October 2026 several hundred French supermarkets had refrigeration warmed up via Danfoss AK-SM system managers. The Danfoss weakness was a second login path reached through undocumented attributes in xml.cgi requests, accepting a daily code derived from the device date with no per-device secret (CVE-2025-41450, CISA ICSA-25-140-03; fixed in Danfoss release 4.2). Impact was achieved by forcing defrost heaters on and disabling alarms; fires were reported. These details are context only and are not stated to apply to RDM. Attribution for the Danfoss attacks is unknown. No IOCs (IPs, domains, hashes) have been published for the RDM issue, so no BeaconBeagle C2 correlation was possible.

MITRE ATT&CK techniques by tactic:

Initial Access

T1190 Exploit Public-Facing Application

Reconnaissance

T1596.005 Scan Databases

Remediation

Patches

  • Apply the latest RDM firmware referenced in advisory RDM-SA-2026-001

Immediate actions

  • Verify RDM controllers are not reachable from the public internet, including via cellular modems with public IP addresses
  • Inventory third-party contractor-installed controllers and modems that the organisation may not own or see
  • Review RDM advisory RDM-SA-2026-001 (2 Nov 2026, revised 3 Nov 2026) and the NCSC urgent alert for retail operators

Workarounds

  • Place cellular modems on a VPN or private APN
  • Restrict remote access to VPN plus IP allowlist

Longer-term hardening

  • Bring contractor remote access under owned, documented and controlled network paths
  • Segment refrigeration/OT networks from business networks and monitor controller traffic
  • Change default and known credentials on controllers and modems

Affected and fixed versions

  • RDM (Resource Data Management) — Refrigeration controllers (models not disclosed)
    Vulnerable versions: Versions not disclosed; firmware prior to the release referenced in RDM-SA-2026-001
    Fixed in: New firmware per RDM-SA-2026-001 (version not disclosed)

Timeline

  • CISA publishes ICSA-25-140-03 for Danfoss AK-SM 8xxA (Claroty Team82 research), including CVE-2025-41450 datetime-based password generation authentication bypass
  • CISA ICSA-25-140-03 Update A adds CVE-2025-41451 and CVE-2025-41452 for Danfoss AK-SM 8xxA
  • Overnight, refrigeration in several hundred French supermarkets is forced to warm via Danfoss AK-SM controllers; fires reported; similar reports from other European countries
  • CERT-FR issues alert CERTFR-2026-ALE-012 on the Danfoss refrigeration controller attacks
  • Pen Test Partners publishes analysis of the Danfoss incident, warning of copycats and internet-exposed controllers
  • RDM issues customer advisory RDM-SA-2026-001 and new firmware after Omega Solutions and Pen Test Partners report vulnerabilities in RDM controllers
  • RDM revises advisory RDM-SA-2026-001
  • CISA revises ICSA-25-140-03 (updated remediation URLs)
  • Pen Test Partners publicly discloses the RDM issue without exploit details; notes NCSC urgent alert to UK supermarkets and remaining exposure at smaller cold chain operators

Sources cited

Drafted by the Threadlinqs research pipeline from 9 sources; published ; last updated —.

Threadlinqs Intelligence — Real-Time Threat Detection Platform

// threat_feed
$ sort --newest
Showing all threats

Live intelligence console

Threat level

Latest Threats