Threat reportICS/SCADATL-2026-3570
CVE-2025-13901: Schneider Electric Modicon M241/M251/M262 Machine Expert Protocol Partial Denial of Service (CWE-404)
An unauthenticated network attacker can send a malicious payload to Schneider Electric Modicon M241, M251 and M262 controllers that occupies active communication channels, causing a partial denial of service on the Machine Expert protocol. Fixed firmware is delivered with EcoStruxure Machine Expert v2.5 / v2.5.0.1; no public exploitation was reported to CISA. First disclosed .
Key facts
| Identifiers | TL-2026-3570, CVE-2025-13901 |
|---|---|
| Also known as | SEVD-2026-069-01, ICSA-26-078-01 |
| Severity | MEDIUM |
| CVSS | 5.3 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L) |
| First disclosed | |
| EPSS | CVE-2025-13901: 0.4% (41.7th percentile) |
| Affected products | Schneider Electric Modicon M241; Schneider Electric Modicon M251; Schneider Electric Modicon M262 |
| Weaknesses (CWE) | CWE-404 |
| Tools | EcoStruxure Machine Expert |
| MITRE ATT&CK techniques | T0814 Denial of Service, T1046 Network Service Discovery, T1499.002 Service Exhaustion Flood, T1595 Active Scanning |
| Motivation | UNKNOWN |
| Target sectors | commercial facilities, critical manufacturing, energy |
| Target regions | Worldwide |
| Detection rules | 9 (1 shown free) |
| Sources | 9 cited sources |
Detection coverage
As of 2026-10-15, Threadlinqs Intelligence publishes 9 detection rule(s) for TL-2026-3570 across Splunk SPL, Microsoft KQL and Sigma, covering 10 indicator(s) of compromise. The whole corpus is readable without an account. Every threat comes with one complete detection in Splunk SPL, Microsoft KQL and Sigma, free for everyone; a free account adds daily TL Creds to unlock the rest. Paid plans add a larger daily allowance, correlation and the MCP server. Threadlinqs MCP server · View plans.
Free detection: CVE-2025-13901 Modicon M241/M251/M262 Exploitation — Machine Expert Channel Exhaustion (Splunk SPL)
Detects a single source opening large numbers of (or long-held) sessions to Machine Expert protocol ports TCP 1105/11740, the behavioural signature of the CVE-2025-13901 payload occupying a Modicon M241/M251/M262 controller's active communication channels (partial DoS, CWE-404). No public exploit signature exists, so detection is behaviour/volume based.
- Languages: Splunk SPL, Microsoft KQL, Sigma
- ATT&CK: T1499.002, T0814, T1499
- Data sources: zeek, firewall, ics_network_traffic
- Severity: medium
- Confidence: medium
Splunk SPL
```CVE-2025-13901 Machine Expert protocol channel exhaustion: many sessions from one source to TCP 1105 / 11740```
index=zeek sourcetype="bro:conn:json" earliest=-15m@m proto=tcp (id.resp_p=1105 OR id.resp_p=11740)
| rename id.orig_h as src, id.resp_h as dest, id.resp_p as dest_port, id.orig_p as src_port
| eval held=if(duration>60 OR conn_state="S1",1,0)
| bin _time span=5m
| stats count as sessions, sum(held) as held_sessions, dc(src_port) as distinct_src_ports, values(dest_port) as dest_ports by _time, src, dest
| where sessions>=50 OR held_sessions>=20
| sort - sessionsMicrosoft KQL
// CVE-2025-13901: connection flood / channel exhaustion against Machine Expert ports
CommonSecurityLog
| where TimeGenerated > ago(1h)
| where DestinationPort in (1105, 11740) and Protocol =~ "TCP"
| summarize Sessions = count(), DistinctSrcPorts = dcount(SourcePort), Actions = make_set(DeviceAction, 5) by SourceIP, DestinationIP, DestinationPort, bin(TimeGenerated, 5m)
| where Sessions >= 50
| project TimeGenerated, SourceIP, DestinationIP, DestinationPort, Sessions, DistinctSrcPorts, Actions
| order by Sessions descSigma
title: Machine Expert Protocol Connection Flood to Modicon Controller (CVE-2025-13901)
id: 7c1d4e52-3b8a-4f06-9a1e-5d2b6c9f0a31
status: experimental
description: Base rule matching connections to Machine Expert ports TCP 1105/11740 on Schneider Modicon M241/M251/M262; paired with the event_count correlation rule below to flag channel exhaustion from a single source.
references:
- https://www.cisa.gov/news-events/ics-advisories/icsa-26-078-01
- https://www.se.com/us/en/download/document/SEVD-2026-069-01/
- https://nvd.nist.gov/vuln/detail/CVE-2025-13901
author: Threadlinqs Team
date: 2026-10-15
tags:
- attack.impact
- attack.t1499.002
- attack.t1499
- attack.inhibit_response_function
- attack.t0814
- cve.2025.13901
logsource:
category: firewall
detection:
selection:
dst_port:
- 1105
- 11740
condition: selection
falsepositives:
- Engineering workstations running EcoStruxure Machine Expert with many open projects
- SCADA/HMI gateways polling controllers over Machine Expert protocol
level: medium
---
title: Machine Expert Protocol Session Burst From Single Source (CVE-2025-13901)
id: 2e9f7a14-6c0b-4d83-b5e7-81a3d4c6f952
status: experimental
description: 50 or more Machine Expert port connections from one source to one controller within 5 minutes.
author: Threadlinqs Team
date: 2026-10-15
correlation:
type: event_count
rules:
- 7c1d4e52-3b8a-4f06-9a1e-5d2b6c9f0a31
group-by:
- src_ip
- dst_ip
timespan: 5m
condition:
gte: 50
level: high
Known false positives:
- Engineering workstation or SCADA/HMI gateway legitimately holding many Machine Expert sessions
- Vulnerability scanners (e.g. Tenable OT plugin 505515) probing the controller ports
Tuning notes: Baseline normal session counts per controller and raise/lower the 50-session / 20-held-session thresholds; add an allowlist lookup of engineering workstation IPs. Zeek logs conn records at session end, so held sessions appear after timeout.
- CVE-2025-13901 Modicon M241/M251/M262 Exploitation — Machine Expert Channel Exhaustion (Sentinel KQL) · unlock with TL Creds
- CVE-2025-13901 Modicon M241/M251/M262 Post-Exploitation — Controller Availability Loss on Machine Expert Ports (Sentinel KQL) · unlock with TL Creds
- CVE-2025-13901 Modicon M241/M251/M262 Reconnaissance — Machine Expert Port Sweeps and Non-Private Sources (Sentinel KQL) · unlock with TL Creds
- CVE-2025-13901 Modicon M241/M251/M262 Exploitation — Machine Expert Channel Exhaustion (Sigma) · unlock with TL Creds
- CVE-2025-13901 Modicon M241/M251/M262 Post-Exploitation — Non-Engineering Process Using Machine Expert Ports (Sigma) · unlock with TL Creds
- CVE-2025-13901 Modicon M241/M251/M262 Reconnaissance — Machine Expert Ports Reached From Non-Private Source (Sigma) · unlock with TL Creds
- CVE-2025-13901 Modicon M241/M251/M262 Post-Exploitation — Controller Availability Loss on Machine Expert Ports (Splunk SPL) · unlock with TL Creds
- CVE-2025-13901 Modicon M241/M251/M262 Reconnaissance — Machine Expert Port Sweeps and Non-Private Sources (Splunk SPL) · unlock with TL Creds
Indicators of compromise
As of 2026-10-15, Threadlinqs Intelligence tracks 10 indicators of compromise for TL-2026-3570.
Technical analysis
CVE-2025-13901 is a CWE-404 (Improper Resource Shutdown or Release) weakness in the Machine Expert protocol implementation of Schneider Electric Modicon M241, M251 and M262 programmable logic controllers. Per the vendor advisory SEVD-2026-069-01 and CISA advisory ICSA-26-078-01, an unauthenticated attacker who can reach the controller over the network can send a malicious payload that occupies the controller's active communication channels, producing a partial denial of service on the Machine Expert protocol. The vendor warns that failing to remediate may risk a denial-of-service attack resulting in loss of availability of the controller.
Scoring: CVSS 3.1 base 5.3 (Medium), vector CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L; NVD also records CVSS 4.0 base 6.9 (Medium), vector CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:L/SC:N/SI:N/SA:N. Impact is limited to availability (low); there is no confidentiality or integrity impact. The Machine Expert protocol is the engineering/programming channel used by EcoStruxure Machine Expert and is documented by Schneider as using TCP 1105 and 11740 and UDP 1740-1743 (11740 is the Fast TCP port used with M262).
Affected: Modicon M241 and M251 firmware prior to 5.4.13.12; Modicon M262 firmware prior to 5.4.10.12. Fixes: M251 firmware 5.4.13.12 delivered with EcoStruxure Machine Expert v2.5.0.1 (CISA lists the v2.5.0.1 installer as the update path for the family); M262 firmware 5.4.10.12 delivered with EcoStruxure Machine Expert v2.5. Vendor mitigations: deploy controllers only in protected environments with minimal network exposure, filter ports and IPs via the embedded firewall, use encrypted communication links, use VPN tunnels for remote access, and isolate control system networks behind firewalls from business networks.
The issue was reported by Amir Zaltzman of Claroty Team82 and is listed on the Team82 disclosure dashboard. CISA reports no known public exploitation and lists affected sectors as Commercial Facilities, Critical Manufacturing and Energy, deployed worldwide. No public PoC, specific exploit payload format, or threat-actor activity is documented in the sources; the MITRE mappings below are therefore limited to the technique classes implied by the advisory's attack description.
MITRE ATT&CK techniques by tactic:
Inhibit Response Function
Discovery
T1046 Network Service Discovery
Impact
T1499.002 Service Exhaustion Flood
Reconnaissance
Remediation
Patches
- Modicon M241/M251: update firmware to 5.4.13.12 or later via EcoStruxure Machine Expert v2.5.0.1
- Modicon M262: update firmware to 5.4.10.12 or later via EcoStruxure Machine Expert v2.5
Immediate actions
- Restrict network access to Machine Expert protocol ports (TCP 1105, TCP 11740, UDP 1740-1743) using the controller's embedded firewall and upstream firewalls
- Ensure controllers are not exposed to the Internet or business networks
Workarounds
- Filter ports and IP addresses with the controller embedded firewall
- Restrict Machine Expert protocol access to trusted engineering workstations
Longer-term hardening
- Deploy controllers only in protected environments with minimal network exposure
- Use encrypted communication links and VPN tunnels for remote access
- Isolate control system networks behind firewalls from business networks
- Monitor ICS network traffic for abnormal connection counts to controller engineering ports
Affected and fixed versions
- Schneider Electric — Modicon M241
Vulnerable versions: firmware prior to 5.4.13.12
Fixed in: 5.4.13.12 - Schneider Electric — Modicon M251
Vulnerable versions: firmware prior to 5.4.13.12
Fixed in: 5.4.13.12 (EcoStruxure Machine Expert v2.5.0.1) - Schneider Electric — Modicon M262
Vulnerable versions: firmware prior to 5.4.10.12
Fixed in: 5.4.10.12 (EcoStruxure Machine Expert v2.5)
Timeline
- Affected versions recorded as Modicon M241/M251 prior to 5.4.13.12 and M262 prior to 5.4.10.12
- CVE-2025-13901 published in NVD (CWE-404; CVSS 3.1 5.3 and CVSS 4.0 6.9) referencing Schneider Electric advisory SEVD-2026-069-01
- CISA publishes ICS advisory ICSA-26-078-01 for Modicon M241, M251 and M262, crediting Amir Zaltzman of Claroty Team82; no known public exploitation reported
- Claroty Team82 publicly discloses the Modicon M241, M251 and M262 vulnerabilities (listed on its disclosure dashboard) that can lead to a denial-of-service condition on the controller
- Schneider Electric SEVD-2026-069-01 document version 1.1 lists remediation: firmware 5.4.13.12 (M251, Machine Expert v2.5.0.1) and 5.4.10.12 (M262, Machine Expert v2.5)
- Tenable OT Security publishes remote detection plugin locked-ioc-2 (plugin 505515); no known exploits reported
- NVD record for CVE-2025-13901 last modified
- Tenable OT plugin 505515 updated to version 1.4
Sources cited
- CISA ICS Advisory ICSA-26-078-01: Schneider Electric Modicon M241, M251, and M262 CISA · Government advisory · 2026-03-19
- NVD - CVE-2025-13901 NVD (NIST) · Advisory · 2026-03-10
- SEVD-2026-069-01 - Vulnerability-Lookup (CIRCL) vulnerability.circl.lu · Advisory
- OpenCVE - CVE-2025-13901 app.opencve.io · Advisory
- Claroty Team82 Disclosure Dashboard - CVE-2025-13901 it.claroty.com · Research
- Schneider Electric SEVD-2026-069-01: Improper Resource Shutdown or Release vulnerability in Multiple Products se.com · Vendor report · 2026-03-31
- Schneider Electric SEVD-2026-069-01 (PDF) download.schneider-electric.com · Vendor report · 2026-03-31
- Tenable OT Security plugin 505515 - Schneider Electric Modicon M241, M251, and M262 Improper Resource Shutdown or Release (CVE-2025-13901) Tenable · Research · 2026-06-23
- Schneider Electric FAQ: Connecting to M262 from EcoStruxure Machine Expert (ports 1105 / 11740) se.com · Vendor report
Other reports on CVE-2025-13901
Previous and next in ics scada
Drafted by the Threadlinqs research pipeline from 9 sources; published ; last updated —.